COMMUNICATION

12.3.3Data/Stop

The data size and stop bits of the equipment connected to this port determine the number of bits transmitted per ASCII character. The data size and stop bits you specify depend on the configuration of your equipment.

For Port 1, the data size must be set to 8, with 1 or 2 stop bits. Settings of 7 data bits/1 stop bit and 7 data bits/2 stop bits are available for Port 2.

NOTE When connecting a computer running a terminal emulation program, set your equipment to NO PARITY.

12.3.4Handshaking

This setting controls handshaking. You can select XON/XOFF or Disabled for this setting.

SXON/XOFF – If handshaking is enabled, the UPS uses special characters (XON and XOFF) to handshake with the host terminal. The XON character is defined to be ASCII value 11 hex, and the XOFF character is defined to be ASCII value 13 hex. Upon reception of an XOFF command, the UPS halts transmission until an XON command is received. In the same way, if the terminal receives an XOFF command, the UPS expects the terminal to halt transmission until the UPS sends an XON command.

SDisabled (No Handshaking) – If handshaking is disabled, the UPS transmits and receives data via the serial port, ignoring all inputs from handshaking lines.

12.3.5Save

Set to YES to save any changes to configuration settings upon exit from the Setup screen. Set to NO if you do not want to save any changes.

12.3.6Default Settings

The following are the default configuration settings for the serial communication ports:

Port 1

Remote Monitor

300 baud

8/1

Handshaking Disabled

 

 

 

 

 

Port 2

Terminal

9600 baud

8/1

Handshaking Disabled

 

 

 

 

 

Each communication port on the UPS operates in one of five modes that you select when configuring the port using the Setup Port screen.