Appendix A | Installation Reference |
gur
The information in this appendix will help you plan for and install the Powerware
9315. This appendix contains the following information:
SPhysical features and requirements, including dimensions
SUPS system oneline configurations
SPower wiring installation notes
SLocation of UPS terminals, including the Inverter/Rectifier, Output/Inverter, and Module Bypass Cabinets (MBCs)
SCustomer interface wiring notes
STypical remote emergency
SRemote Monitor Panel (RMP) dimensions
SRelay Interface Module (RIM) dimensions
SSupervisory Contact Module (SCM) dimensions
SBattery disconnect switch dimensions
A.1 Physical Features and Requirements
1.The UPS equipment operating environment must meet the size and weight requirements shown in Table A, according to your UPS system configuration.
2.In the UPS system, the UPS, Input/Rectifier, Output/Inverter, and MBC or System Bypass Module (SBM) are palleted separately for shipping.
3.Do not tilt the UPS or optional cabinets more than 10° from vertical or the cabinet may tip over.
4.Dimensions are in millimeters [inches].
Table A. Equipment Weight
|
| Weight |
|
Powerware 9315 Component |
| kg (lb) |
|
|
|
| |
| Shipping | Installed | |
|
|
|
|
Power Control Module (PCM) 1 (Input/Rectifier) | 2818 (6200) | 2682 | (5900) |
|
|
|
|
PCM 2 (Output/Inverter) | 2909 (6400) | 2773 | (6100) |
|
|
|
|
PCM 3 (MBC) | 272.7 (600) | 250 | (550) |
|
|
|
|
5.The clearances required around the UPS cabinet are shown in Table B.
Table B. UPS Cabinet Clearances
From the Top of the Cabinet | Minimum clearance over the UPS cabinet is 30.5 cm (12”) |
|
|
From the Front of the Cabinet | 91.4 cm (36”) working space |
|
|