STable 4‐1 details the power cable terminations.

INSTALLING A REMOTE BATTERY DISCONNECT

SNominal voltages listed in this chapter are for a lead‐acid batteries rated per NEC at 2.00 Vdc per cell.

SBattery strings must be installed according to all applicable codes and regulations, including NEC, Article 480.

SThe UPS to battery cable should be sized for a total maximum voltage drop of 1% nominal DC Link voltage at maximum current.

STable 4‐1 details the power cable terminations.

SThe remote battery disconnect weighs approximately 60.3 kg (133 lb). It has an ampere interrupting capacity (AIC) of 100,000 at 500 Vdc.

Table 4‐1. Remote Battery Disconnect Power Terminations

Number and Type of Accessories Permitted

Terminal

Terminal Function

Size of Termination

Tightening Torque

Bolt Size

Nm (lb ft)

 

 

 

 

 

 

 

 

 

E4 (+)

UPS Battery Input (+)

See Table H on page A-16

 

 

 

 

 

E5 (–)

UPS Battery Input (–)

See Table H on page A-16

 

 

 

 

 

 

Breaker (+)

Battery Disconnect (+)

8 – 1 Bolt Mounting

76 (56)

1/2”

 

 

Bus Bar

 

 

 

 

 

 

 

Breaker (–)

Battery Disconnect (–)

8 – 1 Bolt Mounting

76 (56)

1/2”

 

 

Bus Bar

 

 

 

 

 

 

 

Breaker (jumper)

Battery Disconnect

8 – 1 Bolt Mounting

76 (56)

1/2”

 

(jumper)

Bus Bar

 

 

 

 

 

 

 

Table 4‐2. Remote Battery Disconnect Circuit Breaker Ratings

UPS Model

Circuit Breaker Rating

DC Voltage

 

 

 

9315‐750/500

1600

384

 

 

 

9315‐750/625

2000

384

 

 

 

9315‐750/750

2500

384

 

 

 

4-2

EATON Powerware® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com