INSTALLING A REMOTE BATTERY DISCONNECT
SNominal voltages listed in this chapter are for a lead‐acid batteries rated per NEC at 2.00 Vdc per cell.
SBattery strings must be installed according to all applicable codes and regulations, including NEC, Article 480.
SThe UPS to battery cable should be sized for a total maximum voltage drop of 1% nominal DC Link voltage at maximum current.
STable 4‐1 details the power cable terminations.
SThe remote battery disconnect weighs approximately 60.3 kg (133 lb). It has an ampere interrupting capacity (AIC) of 100,000 at 500 Vdc.
Table 4‐1. Remote Battery Disconnect Power Terminations
Number and Type of Accessories Permitted
Terminal | Terminal Function | Size of Termination | Tightening Torque | Bolt Size | |
Nm (lb ft) | |||||
|
|
|
| ||
|
|
|
|
| |
E4 (+) | UPS Battery Input (+) | See Table H on page |
| ||
|
|
|
| ||
E5 | UPS Battery Input | See Table H on page |
| ||
|
|
|
|
| |
Breaker (+) | Battery Disconnect (+) | 8 – 1 Bolt Mounting | 76 (56) | 1/2” | |
|
| Bus Bar |
|
| |
|
|
|
|
| |
Breaker | Battery Disconnect | 8 – 1 Bolt Mounting | 76 (56) | 1/2” | |
|
| Bus Bar |
|
| |
|
|
|
|
| |
Breaker (jumper) | Battery Disconnect | 8 – 1 Bolt Mounting | 76 (56) | 1/2” | |
| (jumper) | Bus Bar |
|
| |
|
|
|
|
|
Table 4‐2. Remote Battery Disconnect Circuit Breaker Ratings
UPS Model | Circuit Breaker Rating | DC Voltage |
|
|
|
9315‐750/500 | 1600 | 384 |
|
|
|
9315‐750/625 | 2000 | 384 |
|
|
|
9315‐750/750 | 2500 | 384 |
|
|
|
EATON Powerware® 9315 UPS |