INSTALLATION REFERENCE

6.The basic environmental requirements for UPS system operation are:

S Ambient Temperature Range:

0–40°C (32–104°F)

SRecommended Operating Range: 20–25°C (68–77°F)

S Maximum Relative Humidity:

95%, noncondensing

The UPS ventilation requirements are shown in Table C.

 

Table C. Air Conditioning or Ventilation Requirements During Full Load Operation

 

 

 

 

 

Rating

Input/Output Voltage

 

Heat Rejection

Ventilation Required for

BTU/hr  1000/hr (kg-cal/hr)

Cooling Air Exhaust

 

 

 

 

 

 

 

500 kVA

400/400

 

109 (27.5)

 

625 kVA

400/400

130.8 (33)

1420 liter/sec

 

 

 

625 kVA

480/480, 600/600

109 (27.5)

(3000 cfm)

750 kVA

480/480, 600/600

130.8 (33)

 

 

 

 

MBC

 

 

Output/Inverter

 

 

 

Cabinet

 

Input/Rectifier

 

 

 

Cabinet

 

 

Figure A‐1. Typical Powerware 9315 (500–750 kVA) UPS System

A-2

EATON Powerware® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com

Page 112
Image 112
Powerware operation manual Figure A‐1. Typical Powerware 9315 500-750 kVA UPS System, 400/400