INSTALLING OPTIONAL ACCESSORIES
Connect to |
|
Port 1 (DB‐9) on |
|
Customer Interface Panel | Fuse |
Terminal Block (TB3)
Figure 6‐4. Terminal Block Bracket
6.Connect RIM wiring to the terminal block using the terminations shown in Table 6‐3.
Table 6‐3. RIM Wire Terminations
From RIM A | To UPS | Remarks |
|
|
|
TB1‐4 | TB3‐1 |
|
|
|
|
TB1‐5 | TB3‐2 | Twisted wires (4) |
|
| |
TB1‐6 | TB3‐3 | |
| ||
|
|
|
TB1‐7 | TB3‐4 |
|
|
|
|
From RIM B (If Used) | To UPS | Remarks |
|
|
|
TB1‐4 | TB3‐5 |
|
|
|
|
TB1‐5 | TB3‐6 | Twisted wires (4) |
|
| |
TB1‐6 | TB3‐7 | |
| ||
|
|
|
TB1‐7 | TB3‐8 |
|
|
|
|
7.Contact your Eaton service representative for verification and testing of the RIM and its connections prior to making connections to J1 through J4.
You can order interface cables separately for connecting to the 15‐pin D‐sub connectors.
8.Repeat Steps 1 through 7 if you are installing another RIM.
9.If you are installing an SCM in addition to an RIM, proceed to paragraph 6.3; otherwise, secure the access plate on top of the UPS Input/Rectifier cabinet.
EATON Powerware® 9315 UPS |