Powerware Powerware 9315 Repeat Steps 1 through 7 if you are installing another RIM

Models: Powerware 9315

1 154
Download 154 pages 18.66 Kb
Page 44
Image 44
8.Repeat Steps 1 through 7 if you are installing another RIM.

INSTALLING OPTIONAL ACCESSORIES

Connect to

 

Port 1 (DB‐9) on

 

Customer Interface Panel

Fuse

Terminal Block (TB3)

Figure 6‐4. Terminal Block Bracket

6.Connect RIM wiring to the terminal block using the terminations shown in Table 6‐3.

Table 6‐3. RIM Wire Terminations

From RIM A

To UPS

Remarks

 

 

 

TB1‐4

TB3‐1

 

 

 

 

TB1‐5

TB3‐2

Twisted wires (4)

 

 

TB1‐6

TB3‐3

1–2 turns per 3”

 

 

 

 

TB1‐7

TB3‐4

 

 

 

 

From RIM B (If Used)

To UPS

Remarks

 

 

 

TB1‐4

TB3‐5

 

 

 

 

TB1‐5

TB3‐6

Twisted wires (4)

 

 

TB1‐6

TB3‐7

1–2 turns per 3”

 

 

 

 

TB1‐7

TB3‐8

 

 

 

 

7.Contact your Eaton service representative for verification and testing of the RIM and its connections prior to making connections to J1 through J4.

You can order interface cables separately for connecting to the 15‐pin D‐sub connectors.

8.Repeat Steps 1 through 7 if you are installing another RIM.

9.If you are installing an SCM in addition to an RIM, proceed to paragraph 6.3; otherwise, secure the access plate on top of the UPS Input/Rectifier cabinet.

6-6

EATON Powerware® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com

Page 44
Image 44
Powerware Powerware 9315 operation manual Repeat Steps 1 through 7 if you are installing another RIM