COMMUNICATION
12.5.7Battery Test Setup
If Battery Test Setup (option 5) is selected from the Main menu (see page
NOTE If a message stating “Battery Test Requires Calibration” appears, please notify your Eaton service representative for proper calibration.
Battery Test Setup
1.Setup One‐time Delayed Battery Test
2.Setup Monthly Battery Test
3.Setup Quarterly Battery Test
4.Cancel Pending Battery Test
5.Display Next Scheduled Battery Test
6.Return to Main Menu
Enter Selection:
This menu allows you to schedule battery tests, review scheduled battery tests, or cancel pending battery tests. If you select 1, 2, or 3 from this menu, the following menu is displayed:
Enter Starting Month
Enter Day of Week, Sunday = 1,
Enter Week of Month
Enter Hour of Test
Enter Minute of Test
<CR> with no entry will return to Battery Test Setup Menu.
NOTE Follow each entry with a carriage return <CR>.
Enter the information at the prompt with a carriage return to schedule the battery test.
If 4 is selected from the Battery Test Setup menu, you are prompted to enter Y to cancel all pending tests. This selection will only cancel pending tests and will not stop a test currently in progress.
If 5 is selected from the Battery Test Setup menu when a Battery Test is scheduled, the following is displayed:
Next Battery Test Scheduled
WK DAY MON HR:MN
4FRI MAR 15:34
Enter <CR> to return to Battery Test Setup Menu
If 5 is selected from the Battery Test Setup menu when a Battery Test is not scheduled, the following is displayed:
No Battery Test Scheduled
Enter <CR> to return to Battery Test Setup Menu
NOTE The unit will only perform one battery test in any 24 hour period.
EATON Powerware® 9315 UPS |