COMMUNICATION

12.4.2Entire Log [Ctrl]+[P]

The [Ctrl]+[P] key sequence prints the entire UPS Event History Log at the time the data is requested. The printout begins with the oldest alarm entry in the queue and ends with the most recent. Any alarms that occur while the Event History Log is printing are included in chronological order. The Event History Log lists up

to 400 system events. Figure 12‐4 shows a sample Event History Log printout.

 

Uninterruptible Power System

 

 

 

UPS System Normal

 

03 NOV 1997

14:23:45

Alarm:

None

 

 

 

 

 

Notice:

None

 

 

 

 

 

 

Event History Log

 

 

 

 

 

Event Description

 

 

 

MAY 12

16:41:19.3

COMMAND: Keyswitch On

0421

 

 

12

16:41:29.1

STATUS:

Auto Mode

1000

 

2030

12

16:41:42.4

COMMAND:

Rectifier Commanded On

12

16:42:05.5

STATUS:

Inverter On

 

 

2202

12

16:42:46.8

STATUS:

Rectifier On

 

 

 

12

16:43:15.8

STATUS:

Inverter Contactor (3) Closed

12

16:43:42.4

STATUS:

Bypass Contactor (K4) Open

12

16:44:29.1

STATUS:

Inverter Normal

4001

 

32

JUN 04 12:16:35.9

NOTICE:

Room High Temperature

 

 

 

 

Figure 12‐4. Event History Log

 

 

 

EATON Powerware® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com

12-7

Page 93
Image 93
Powerware Powerware 9315 operation manual Entire Log Ctrl+P, ‐4. Event History Log