Powerware Powerware 9315 Basic Unit Rating, Units, Rating 50/60 Hz, Input and Output Voltage

Models: Powerware 9315

1 154
Download 154 pages 18.66 Kb
Page 124
Image 124

INSTALLATION REFERENCE

Table F. Input/Output Ratings and External Wiring Requirements (PW9315-700/500 and PW9315-750/562)

Basic Unit Rating

 

Units

 

Rating 50/60 Hz

 

PW9315-750/500 at 0.8 Lagging pF Load

 

 

 

 

 

 

 

kVA/kW

625/500

625/500

625/562

625/562

PW9315-750/562 at 0.9 Lagging pF Load

 

 

 

 

 

 

 

Input and Output Voltage

 

Volts

480

600

480

600

 

 

 

 

 

 

 

AC Input to UPS Rectifier (0.95 Min. pF)

 

Amps*

951

761

984

787

(3) Phases, (1) Neutral, (1) Ground

 

 

 

 

 

 

 

 

A

 

 

 

 

 

Minimum Conductor Size

 

 

 

 

 

Number per Phase

AWG or kcmil

400

350

500

350

 

* Maximum amps includes full load current plus

 

(each)

(4)

(4)

(4)

(4)

battery recharge current

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to MBC (UPS Bypass)

 

 

 

 

 

 

Full Load Current

 

Amps

752

601

752

601

(3) Phases, (1) Neutral, (1) Ground

B

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

500

350

500

350

Number per Phase

 

(each)

(3)

(3)

(3)

(3)

DC Input from Battery to UPS

 

Vdc

384

384

384

384

(1) Positive, (1) Negative

C

Amps @ (2.0V/cell)

1370

1370

1542

1542

 

 

 

 

 

 

Minimum Conductor Size

AWG or kcmil

500

500

600

600

 

Number per Pole

 

(each)

(6)

(6)

(6)

(6)

AC Output to Optional SBM

 

 

 

 

 

 

Full Load Current

 

Amps

752

601

752

601

(3) Phases, (1) Neutral, (1) Ground

E

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

500

350

500

350

Number per Phase

 

(each)

(3)

(3)

(3)

(3)

AC Output to Critical Load

 

 

 

 

 

 

Full Load Current

 

Amps

752

601

752

601

(3) Phases, (1) Neutral, (1) Ground

D

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

500

350

500

350

Number per Phase

 

(each)

(3)

(3)

(3)

(3)

 

 

 

 

 

 

 

NOTE Callout letters A, B, C, D, and E map to Figure A‐8.

A-14

EATON Powerware® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com

Page 124
Image 124
Powerware Powerware 9315 Basic Unit Rating, Units, Rating 50/60 Hz, Input and Output Voltage, AC Input to MBC UPS Bypass