INSTALLATION REFERENCE
Table F. Input/Output Ratings and External Wiring Requirements
Basic Unit Rating |
| Units |
| Rating 50/60 Hz |
| ||
|
|
|
|
|
|
| |
| kVA/kW | 625/500 | 625/500 | 625/562 | 625/562 | ||
| |||||||
|
|
|
|
|
| ||
Input and Output Voltage |
| Volts | 480 | 600 | 480 | 600 | |
|
|
|
|
|
|
| |
AC Input to UPS Rectifier (0.95 Min. pF) |
| Amps* | 951 | 761 | 984 | 787 | |
(3) Phases, (1) Neutral, (1) Ground |
| ||||||
|
|
|
|
|
| ||
| A |
|
|
|
|
| |
Minimum Conductor Size |
|
|
|
|
| ||
Number per Phase | AWG or kcmil | 400 | 350 | 500 | 350 | ||
| |||||||
* Maximum amps includes full load current plus |
| (each) | (4) | (4) | (4) | (4) | |
battery recharge current |
|
|
|
|
|
| |
|
|
|
|
|
|
| |
AC Input to MBC (UPS Bypass) |
|
|
|
|
|
| |
Full Load Current |
| Amps | 752 | 601 | 752 | 601 | |
(3) Phases, (1) Neutral, (1) Ground | B |
|
|
|
|
| |
|
|
|
|
|
| ||
Minimum Conductor Size |
| AWG or kcmil | 500 | 350 | 500 | 350 | |
Number per Phase |
| (each) | (3) | (3) | (3) | (3) | |
DC Input from Battery to UPS |
| Vdc | 384 | 384 | 384 | 384 | |
(1) Positive, (1) Negative | C | Amps @ (2.0V/cell) | 1370 | 1370 | 1542 | 1542 | |
|
|
|
|
|
| ||
Minimum Conductor Size | AWG or kcmil | 500 | 500 | 600 | 600 | ||
| |||||||
Number per Pole |
| (each) | (6) | (6) | (6) | (6) | |
AC Output to Optional SBM |
|
|
|
|
|
| |
Full Load Current |
| Amps | 752 | 601 | 752 | 601 | |
(3) Phases, (1) Neutral, (1) Ground | E |
|
|
|
|
| |
|
|
|
|
|
| ||
Minimum Conductor Size |
| AWG or kcmil | 500 | 350 | 500 | 350 | |
Number per Phase |
| (each) | (3) | (3) | (3) | (3) | |
AC Output to Critical Load |
|
|
|
|
|
| |
Full Load Current |
| Amps | 752 | 601 | 752 | 601 | |
(3) Phases, (1) Neutral, (1) Ground | D |
|
|
|
|
| |
|
|
|
|
|
| ||
Minimum Conductor Size |
| AWG or kcmil | 500 | 350 | 500 | 350 | |
Number per Phase |
| (each) | (3) | (3) | (3) | (3) | |
|
|
|
|
|
|
|
NOTE Callout letters A, B, C, D, and E map to Figure A‐8.
EATON Powerware® 9315 UPS |