INSTALLATION REFERENCE

Table E. Input/Output Ratings and External Wiring Requirements (PW9315-625/400, PW9315-625/450, PW9315-625/500, and PW9315-625/562)

Basic Unit Rating

 

Units

 

Rating 50/60 Hz

 

PW9315-625/400 and PW9315-625/500 at 0.8 Lagging pF Load

 

 

 

 

 

kVA/kW

500/400

500/450

625/500

625/562

PW9315-625/450 and PW9325-625/562 at 0.9 Lagging pF Load

 

 

 

 

 

Input and Output Voltage

 

Volts

400

400

400

400

 

 

 

 

 

 

 

AC Input to UPS Rectifier (0.95 Min. pF)

 

Amps*

880

910

1100

1138

(3) Phases, (1) Neutral, (1) Ground

 

 

 

 

 

 

 

 

A

 

 

 

 

 

Minimum Conductor Size

 

 

 

 

 

Number per Phase

AWG or kcmil

350

400

600

700

 

* Maximum amps includes full load current plus

 

(each)

(4)

(4)

(4)

(4)

battery recharge current

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to MBC (UPS Bypass)

 

 

 

 

 

 

Full Load Current

 

Amps

722

722

902

902

(3) Phases, (1) Neutral, (1) Ground

B

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

300

300

500

500

Number per Phase

 

(each)

(4)

(4)

(4)

(4)

DC Input from Battery to UPS

 

Vdc

384

384

384

384

(1) Positive, (1) Negative

C

Amps @ (2.0V/cell)

1096

1234

1371

1542

 

 

 

 

 

 

Minimum Conductor Size

AWG or kcmil

400

500

400

700

 

Number per Pole

 

(each)

(4)

(5)

(5)

(5)

AC Output to Optional SBM

 

 

 

 

 

 

Full Load Current

 

Amps

722

722

902

902

(3) Phases, (1) Neutral, (1) Ground

E

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

300

300

500

500

Number per Phase

 

(each)

(4)

(4)

(4)

(4)

AC Output to Critical Load

 

 

 

 

 

 

Full Load Current

 

Amps

722

722

902

902

(3) Phases, (1) Neutral, (1) Ground

D

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

300

300

500

500

Number per Phase

 

(each)

(4)

(4)

(4)

(4)

 

 

 

 

 

 

 

NOTE Callout letters A, B, C, D, and E map to Figure A‐8.