INSTALLATION REFERENCE
Table E. Input/Output Ratings and External Wiring Requirements
Basic Unit Rating |
| Units |
| Rating 50/60 Hz |
| ||
|
|
|
|
| |||
kVA/kW | 500/400 | 500/450 | 625/500 | 625/562 | |||
|
|
|
|
| |||
Input and Output Voltage |
| Volts | 400 | 400 | 400 | 400 | |
|
|
|
|
|
|
| |
AC Input to UPS Rectifier (0.95 Min. pF) |
| Amps* | 880 | 910 | 1100 | 1138 | |
(3) Phases, (1) Neutral, (1) Ground |
| ||||||
|
|
|
|
|
| ||
| A |
|
|
|
|
| |
Minimum Conductor Size |
|
|
|
|
| ||
Number per Phase | AWG or kcmil | 350 | 400 | 600 | 700 | ||
| |||||||
* Maximum amps includes full load current plus |
| (each) | (4) | (4) | (4) | (4) | |
battery recharge current |
|
|
|
|
|
| |
|
|
|
|
|
|
| |
AC Input to MBC (UPS Bypass) |
|
|
|
|
|
| |
Full Load Current |
| Amps | 722 | 722 | 902 | 902 | |
(3) Phases, (1) Neutral, (1) Ground | B |
|
|
|
|
| |
|
|
|
|
|
| ||
Minimum Conductor Size |
| AWG or kcmil | 300 | 300 | 500 | 500 | |
Number per Phase |
| (each) | (4) | (4) | (4) | (4) | |
DC Input from Battery to UPS |
| Vdc | 384 | 384 | 384 | 384 | |
(1) Positive, (1) Negative | C | Amps @ (2.0V/cell) | 1096 | 1234 | 1371 | 1542 | |
|
|
|
|
|
| ||
Minimum Conductor Size | AWG or kcmil | 400 | 500 | 400 | 700 | ||
| |||||||
Number per Pole |
| (each) | (4) | (5) | (5) | (5) | |
AC Output to Optional SBM |
|
|
|
|
|
| |
Full Load Current |
| Amps | 722 | 722 | 902 | 902 | |
(3) Phases, (1) Neutral, (1) Ground | E |
|
|
|
|
| |
|
|
|
|
|
| ||
Minimum Conductor Size |
| AWG or kcmil | 300 | 300 | 500 | 500 | |
Number per Phase |
| (each) | (4) | (4) | (4) | (4) | |
AC Output to Critical Load |
|
|
|
|
|
| |
Full Load Current |
| Amps | 722 | 722 | 902 | 902 | |
(3) Phases, (1) Neutral, (1) Ground | D |
|
|
|
|
| |
|
|
|
|
|
| ||
Minimum Conductor Size |
| AWG or kcmil | 300 | 300 | 500 | 500 | |
Number per Phase |
| (each) | (4) | (4) | (4) | (4) | |
|
|
|
|
|
|
|
NOTE Callout letters A, B, C, D, and E map to Figure A‐8.
EATON Powerware® 9315 UPS |