PRODUCT SPECIFICATIONS

14.3 UPS System Output

 

 

 

 

 

DC Filtering

Ripple voltage less than 0.5% peak to peak

 

 

 

 

UPS Output Capacity

100% rated current at 0.8 power factor or 100% rated current at 0.9 power

 

 

factor

 

Output Voltage Regulation

1% (10% to 100% load)

 

 

 

 

Output Voltage

600 Vac nominal, adjustable from 570 Vac to 630 Vac (60 Hz only)

 

Adjustment

480 Vac nominal, adjustable from 456 Vac to 504 Vac (60 Hz only)

 

(Nominal +/–5%)

400 Vac nominal, adjustable from 380 Vac to 420 Vac (50/60 Hz)

 

 

 

 

Output Voltage Harmonic

3% max THD, 2% max single (linear load)

 

Content

 

 

 

 

 

Output Voltage Balance

3% for 100% maximum load imbalance (linear load)

 

 

 

 

Output Voltage Phase

3° for 100% maximum load imbalance (linear load)

 

Displacement

 

 

 

 

 

Output Transients

"5% for 100% load step or removal

 

 

 

 

Frequency Regulation

"0.01 Hz free running

 

 

 

 

Synchronous to Bypass

Bypass within voltage limits of +5%, –8% of output setting; bypass within

 

 

"0.5 Hz

 

Frequency Slew Rate

1 Hz per second maximum (adjustable)

 

 

 

 

Overload Capability

125% for 10 minutes

 

 

150% for 10 seconds

 

Maximum Output

300% peak for 10 cycles without bypass

 

Capability

 

 

 

 

14.4 Environmental Specifications

Operating Temperature

0 to 40°C (32–104°F) without derating. The recommended operating

 

temperature is 25°C (77°F).

Operating Altitude

Maximum 1500m (5000 ft) at 40°C without derating

 

 

Storage Temperature

–20 to +70°C (prolonged storage above 40°C will cause rapid battery

 

self‐discharge)

Relative Humidity

95% maximum noncondensing

(Operating and Storage)

 

 

 

Acoustical Noise

75 dBA at a 1m distance

 

 

Electrostatic Discharge

Meets IEC 801‐2 specifications.

(ESD) Immunity

 

 

 

14-2

EATON Powerware® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com

Page 108
Image 108
Powerware Powerware 9315 UPS System Output, Environmental Specifications, DC Filtering, UPS Output Capacity, factor