Powerware Powerware 9315 operation manual ‐2. Terminal Block Bracket, Connect to Port 1 DB‐9 on

Models: Powerware 9315

1 154
Download 154 pages 18.66 Kb
Page 41
Image 41
Connect to Port 1 (DB‐9) on

INSTALLING OPTIONAL ACCESSORIES

To install an RMP:

1.Verify that the UPS system is turned off and all power sources are removed. See Chapter 9, “UPS Operating Instructions,” for shutdown instructions.

2.Remove the access plate on top of the UPS Input/Rectifier cabinet to gain access to the customer interface panel (see Figure A‐13 on page A-23).

3.Securely mount the RMP.

4.Install wiring from the RMP using ½” conduit through the cable entry knockout in the top of the UPS Input/Rectifier cabinet. See Figure A‐13 on page A-23for the conduit landing area location.

5.In the spare parts kit, locate the RMP adapter cable assembly (see Figure 6‐2). Mate the DB‐9 connector on the back of the terminal block to the DB‐9 connector (Port 1) on the UPS customer interface panel (see Figure A‐19 on page A-30). Use two screws from the spare parts kit to secure the terminal block bracket to the customer interface panel.

Connect to Port 1 (DB‐9) on

Customer Interface Panel

Fuse

Terminal Block (TB3)

Figure 6‐2. Terminal Block Bracket

EATON Powerware® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com