INSTALLATION REFERENCE

Table J. Recommended Installation Parts and Tool (Not Supplied by Eaton)

Part

Size

Quantity

Manufacturer

Part Number

Notes

 

 

 

 

 

 

Long Barrel 2 Hole Lug

500 MCM

As required

Thomas & Betts

54876BE

Color Code: Brown

 

Die Code: 87

 

 

 

 

 

 

 

 

 

 

 

Bolt, Grade 5

1/2” 2”

1

N/A

N/A

 

 

 

 

 

 

 

Flat Washer

1/2”

1

N/A

N/A

 

 

 

 

 

 

Quantity per lug hole

Lock Washer

1/2”

1

N/A

N/A

 

 

 

 

 

 

 

Nut

1/2”

1

N/A

N/A

 

 

 

 

 

 

 

Manual Hydraulic Crimp Tool

14 Ton

1

Thomas & Betts

TBM14M

 

 

 

 

 

 

 

Die Set

N/A

1

Thomas & Betts

15506

 

 

 

 

 

 

 

13.Standard breakers used in the UPS are rated for 65 KAIC, with optional breakers rated for 100 KAIC. To prevent cable whipping, secure cables as shown in Figure A‐10. Wrap line cables together with nominal 9.5 mm (3/8”) nylon rope or rope having a minimum tensile strength of 8896 N (2000 pounds). Wrap line cables at 152 mm (6”) and 1305 mm (2”) from the line terminals with 5 wraps. Wrap each additional 152.4 mm (6”) interval with

5 wraps or 25.4 mm (1”) intervals with 1 wrap.

NYLON ROPE -9 MM [3/8

INCH] DIAMETER.

MINIMUM OF FIVE WRAPS.

152 MM [6 INCHES]

Figure A‐10. Securing Cables

A-18

EATON Powerware® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com

Page 128
Image 128
Powerware Powerware 9315 operation manual Figure A‐10. Securing Cables, Part Size Quantity Manufacturer