INSTALLATION REFERENCE
AC INPUT TO | AC INPUT TO | AC INPUT TO | AC INPUT TO | AC INPUT TO |
MODULE #n | MODULE #2 | MODULE #1 | SYSTEM BYPASS | MAINT. BYPASS |
3 PHASE, | 3 PHASE, | 3 PHASE, | 3 PHASE, | 3 PHASE, |
3 WIRE | 3 WIRE | 3 WIRE | 3 OR 4 WIRE | 3 OR 4 WIRE |
n = LAST UPM IN LINEUP
NOTE A bypass neutral feeder must be supplied when the output neutral is used. If no bypass neutral feeder is supplied, the output neutral of the UPMs are to be connected to chassis ground.
UPS OUTPUT TO
CRITICAL LOAD
3 PHASE, 3 OR 4 WIRE
Figure A‐9. Multi-Module UPS System Oneline Drawing (with Powerware Hot Sync® Capacity, 480/480V and 600/600V Input/Output)
EATON Powerware® 9315 UPS |