| E6580757 | |
|
|
|
|
|
|
|
| [Parameter setting] |
|
|
|
| |
| Title | Function |
| Adjustment range | Default setting |
|
|
|
|
|
|
|
|
|
| DC braking starting frequency | 0.0 ∼ | (Hz) | 0.0 |
|
|
| DC braking current | 0.0 ∼ | 100 (%) | 30.0 |
|
|
| DC braking time | 0.0 ∼ | 20.0 (sec) | 1.0 |
|
Output frequency [Hz]
Set frequency
| DC braking |
DC braking starting frequency |
|
| Time [sec] |
Output current [A] | DC braking current |
|
DC braking time | 6 |
|
Operation signal
Note: During DC braking, the overload protection sensitivity of the inverter increases. The DC braking cur- rent may be adjusted automatically to prevent tripping.
6.8Jog run mode
: Jog run frequency
: Jog run stopping pattern
• Function
Use the jog run parameters to operate the motor in jog mode. Input of a jog run signal generates a jog run frequency output at once, irrespective of the designated acceleration time.
The motor can be operated in jog mode while the jog run setting terminals are connected