E6580757
Application!!
• A waiting time of 200 to 1,000msec is preset to allow the residual voltage in the motor to decrease to a certain level during restart. For this reason, the
• Use this function when operating a system with one motor connected to one inverter. This function may not operate properly in a system configuration with multiple motors connected to one inverter. Application to a crane or hoist
The crane or hoist may have its load moved downward during the above waiting time from input of the operation starting command to the restart of the motor. To apply the inverter to such machines, therefore, set the
6.12.2 Regenerative power ride-through control
: Regenerative power ride-through control
• Function
Regenerative power |
| |||||||
6 | ||||||||
generative energy in the event of momentary power failure. |
|
|
| |||||
|
|
|
| |||||
[Parameter setting] |
|
|
|
|
|
| ||
|
|
|
|
|
| |||
Title |
| Function |
| Adjustment range | Default setting |
|
|
Regenerative power
0: Disabled, 1: Enabled
0
Note: Even when this parameter is set, the particular load conditions may cause the motor to coast. In this case, use the
[When power is interrupted]
Input voltage
Motor speed
★The time for which the operation of the motor can be continued depends on the machine inertia and load conditions. Before using this function, therefore, perform verification tests.
★Use with the retry function allows the motor to be restarted automatically without being brought to an abnormal stop.
★The operation continuing time is about
Approx. 100ms | 100ms when regenerative power ride- | ||
| through control is enabled ( |
| = 1). |
[If momentary power failure occurs]
Input voltage
Motor speed
100ms (maximum)