Toshiba VF-S9 manual An example of setting for displaying the motor speed or load speed

Models: VF-S9

1 198
Download 198 pages 1.97 Kb
Page 136
Image 136
Input (DC) voltage:

E6580757

1) Display in percentage terms

2) Display in amperes/volts

Output current:

Output current:

Input (DC) voltage:

Input (DC) voltage:

 

(vale of changing to AC)

An example of setting for displaying the motor speed or load speed

Set ■An example of setting for displaying the motor speed or load speed to either " Manual background " or " Manual background ".

The value obtained by multiplying the displayed frequency by the Manual background-set value will be displayed as fol- lows:

Value displayed = Monitor-displayed or parameter-set frequency

1)Displaying the motor speed

To switch the display mode from 60Hz (default setting) to 1800min-1 (the rotating speed of the 4P mo- tor)

6

2)Displaying the speed of the loading unit

To switch the display mode from 60Hz (default setting) to 6m/min-1 (the speed of the conveyer)

Note: This parameter displays the inverter output frequency as the value obtained by multiplying it by a positive number. Even when the actual speed of the motor changes according to the particular changes in load, the output frequency will always be displayed.

F-52

Page 136
Image 136
Toshiba VF-S9 manual An example of setting for displaying the motor speed or load speed, Input DC voltage