E6580757

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optional external devices

 

 

 

 

 

 

 

No.

 

Device

 

 

Function and purpose

 

 

 

 

 

 

Input AC reactor

Used to improve the input power factor, reduce the harmonics, and suppress external

 

 

 

 

 

 

surge on the inverter power source side. Install when the power capacity is 500 kVA or

 

 

 

 

 

 

more and 10 times or more than the inverter capacity or when a distorted wave genera-

 

 

 

 

 

 

tion source such as a thyristor unit or a large-capacity inverter is connected in the same

 

 

 

 

 

 

distribution system.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)

 

 

 

 

 

 

Effect

 

 

 

 

 

 

 

 

Reactor type

Power factor

 

Harmonics Suppression

External surge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200V-3.7kW

 

 

 

 

 

 

 

 

 

 

 

improvement

 

 

Other model

suppression

 

 

 

 

 

 

 

 

 

 

 

or less

 

 

 

 

 

 

 

 

 

 

 

Input AC reactor

{

 

{

 

{

{

 

 

 

 

 

 

 

 

DC reactor

{ Large

 

{

 

{ Large

 

 

 

 

 

 

 

 

{ Large : Large effective. { : effective. : ineffective

 

 

 

 

 

 

DC reactor

Improves the power factor more than the input reactor. When the facility applying the

 

 

 

 

 

 

inverter requires high reliability, it is recommended to use the DC reactor with an input re-

 

 

 

 

 

 

actor effective for external surge suppression.

 

 

 

 

 

 

 

(2)

 

 

* An inverter unit of 200V-3.7kW or less is connected to a reactor selected on page J-8, 9

 

 

 

 

 

 

 

to conform “Guides of limits for harmonics current emissions on general purpose

 

 

 

 

 

 

 

inverter having an input current up to and including 20A per phase” by the Japan Elec-

 

 

 

 

 

 

 

trical Manufacturers’ Association.

 

 

 

 

 

 

 

 

 

 

High-attenuation filter

These types of filters are not necessary because all single-phase 200V or 3-phase 400V

 

 

 

 

 

(LC filter)

models and 3-phase 200V, 5.5kW or 7.5kW models have a built-in EMI noise filter, con-

 

 

 

 

 

NF type

forming to Class A, as standard. But install these filters if necessarily of noise reduction

 

 

 

 

 

manufactured by

move and more.

 

 

 

 

 

 

 

 

 

 

(3)

filter

Soshin Electric Co.

Effective to prevent interference in audio equipment used near the inverter.

 

 

 

 

 

Install on the input side of the inverter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reduction

Zero-phase reactor

Provided with wide-range attenuation characteristics from AM radio bands to near

 

 

 

 

Effective to prevent interference in audio equipment used near the inverter.

 

 

 

 

 

 

 

10MHz.

 

 

 

 

 

 

 

 

 

 

 

 

 

Use when equipment readily affected by noise is installed in the peripheral area.

 

 

 

 

noise

(Inductive filter)

Effective in noise reduction on both input and output sides of the inverter.

 

 

 

(4)

Ferrite core type

Provided with attenuation characteristics of several dB in frequencies from AM radio

 

 

 

 

Radio

manufactured by

 

bands to 10MHz.

 

 

 

 

 

 

 

 

 

 

 

Soshin Electric Co.

For noise countermeasures, insert on the secondary side of the inverter.

 

 

 

 

 

 

10

 

 

 

Foot-mounted type

High-attenuation EMI noise filter requiring only small space; mounted on the rear side of

 

 

 

 

noise reduction filter

the inverter. This filter can be installed to conform to the following classes of EMC stan-

 

 

(5)

 

(Soon to be

dard EN5501 Group 1.

 

 

 

 

 

 

 

 

 

 

released)

3-phase 200V models excluding those of 5.5/7.5kW

: Conform to Class A.

 

 

 

 

 

 

All models other than above

 

: Conform to Class B.

 

 

 

 

Braking resistor

Use when rapid deceleration or stop is frequently required or when it is desired to reduce

 

 

 

(6)

 

 

the deceleration time with large load. This resistor consumes regenerative energy during

 

 

 

 

 

power generation braking.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Braking resistor – With (resistor + protective thermal relay) built in.

 

 

 

 

 

 

Motor-end surge voltage

Use an insulation-reinforced motor or install the surge voltage restraint filter to prevent

 

 

 

(7)

suppression filter (400V

degrading motor insulation caused by surge voltage generation depending on cable

 

 

 

 

class only)

length and wiring method, or use of a 400V class motor driven with an inverter.

 

 

 

(8)

Conduit pipe kit

Attachment kit used for conformance to NEMA TYPE1.

 

 

 

 

 

(Soon to be released)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(9)

IP43 enclosure kit

Attachment kit for making a panel conform to the IP43 structure.

 

 

 

 

 

(Soon to be released)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(10)

DIN rail kit

Available for the 200V class models of 0.75kW or less. (Model: DIN001Z)

 

 

 

(Soon to be released)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 