E6580757
■Parameter setting
Title | Function | Adjustment range | Default setting |
|
|
|
|
|
| 0: Standard setting |
|
| RST signal selection | (reset on when | 0 |
| 1: Activated by turning RST off | ||
|
|
| |
|
| (reset on when |
|
6.3 Terminal function selection
6.3.1 Keeping an input terminal function always active (ON)
: Always-active function selection
• Function
This parameter specifies an input terminal function that is always to be kept active (ON). (Only one function selectable)
| ■ Parameter setting |
|
| ||
6 |
|
| |||
| Title | Function | Adjustment range | Default setting | |
|
|
|
|
|
|
|
|
| 0 ∼ 51 (See section 11) | 0 | |
|
|
|
|
|
|
6.3.2Modifying input terminal functions
: Input terminal selection 1 (F)
: Input terminal selection 2 (R)
: Input terminal selection 3 (RST)
: Input terminal selection 4 (S1)
: Input terminal selection 5 (S2) : Input terminal selection 6 (S3)
Use the above parameters to send signals from an external programmable controller to various control input terminals to operate and/or set the inverter.
The desired contact input terminal functions can be selected from 51 types. This gives system design flexi- bility.