Toshiba VF-S9 manual Calorific values of the inverter and the required ventilation

Models: VF-S9

1 198
Download 198 pages 1.97 Kb
Page 30
Image 30
■ Calorific values of the inverter and the required ventilation

E6580757

Note: Do not install in any location where there is high humidity or high temperatures and where there are large amounts of dust, metallic fragments and oil mist. If you are going to install the equipment in any area that presents a potential problem, please consult with Toshiba before doing so.

■ Calorific values of the inverter and the required ventilation

The energy loss when the inverter converts power from AC to DC and then back to AC is about 5 percent. In

 

order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the interior of

 

1

the cabinet must be ventilated and cooled.

 

 

 

The amount of forcible air cooling ventilation required and the necessary heat discharge surface quantity when operating in a sealed cabinet according to motor capacity are as follows.

 

Operating motor

 

 

Calorific Values

Amount of forcible air

Heat discharge surface

Voltage Class

capacity

Inverter Type

Carrier

Carrier

cooling ventilation re-

area required for sealed

 

 

 

 

frequency

frequency

3

2

 

(kW)

 

 

4kHz

12kHz

quired (m /min)

storage cabinet(m )

 

 

 

 

 

 

0.2

 

2002PL

23

29

0.23

0.8

Single-Phase

0.4

 

2004PL

47

60

0.29

1.0

0.75

VFS9S- 2007PL

74

88

0.40

1.4

200V Class

1.5

 

2015PL

142

169

0.60

2.1

 

 

 

2.2

 

2022PL

239

270

0.80

2.8

 

0.2

 

2002PM

21

26

0.23

0.8

 

0.4

 

2004PM

43

54

0.29

1.0

 

0.75

 

2007PM

67

79

0.40

1.4

Single-Phase

1.5

 

2015PM

131

150

0.60

2.1

2.2

VFS9-

2022PM

168

195

0.80

2.8

200V Class

3.7

2037PM

330

374

1.2

4.3

 

 

5.5

 

2055PL

450

510

1.7

6.1

 

7.5

 

2075PL

576

635

2.3

8.1

 

11

 

2110PM

750

820

3.4

12.0

 

15

 

2150PM

942

1035

4.6

16.0

 

0.75

 

2007PL

44

57

0.40

1.4

 

1.5

 

2015PL

77

99

0.60

2.1

Three-Phase

2.2

 

2022PL

103

134

0.80

2.8

3.7

VFS9-

2037PL

189

240

1.2

4.3

400V Class

5.5

2055PL

264

354

1.7

6.1

 

 

7.5

 

2075PL

358

477

2.3

8.1

 

11

 

2110PL

490

650

3.4

12.0

 

15

 

2150PL

602

808

4.6

16.0

Notes

1)The heat loss for the optional external devices (input reactor, DC reactor, radio noise reduction filters, etc.) is not included in the calorific values in the table.

2)Case of 100% Load Continuation operation.

Panel designing taking into consideration the effects of noise.

The inverter generates high frequency noise. When designing the control panel setup, consideration must be given to that noise. Examples of measures are given below.

Wire so that the main circuit wires and the control circuit wires are separated. Do not place them in the same conduit, do not run them parallel, and do not bundle them.

Provide shielding and twisted wire for control circuit wiring.

Separate the input (power) and output (motor) wires of the main circuit. Do not place them in the same conduit, do not run them parallel, and do not bundle them.

Ground the inverter ground terminals (■Panel designing taking into consideration the effects of noise.).

A-19

Page 30