13.Before making a service call
- Trip information and remedies
13.1 Trip causes/warnings and remedies
When a problem arises, diagnose it in accordance with the following table. If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the table, contact your Toshiba dealer.
[Trip information]
Error code | Communication | Problem |
| Possible causes |
|
|
| Remedies |
|
|
|
| No. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 1 | Overcurrent during | • | The acceleration time | is too short. | • | Increase the acceleration time | . |
|
| |
|
| acceleration | • | The V/F setting is improper. |
| • Check the V/F parameter. |
|
|
| ||
|
|
| • A restart signal is input to the rotating | • | Use |
|
|
| |||
|
|
|
| motor after a momentary stop, etc. |
|
|
|
| |||
|
|
| • A special motor (e.g. motor with a small | • | Increase the carrier frequency | . |
|
| |||
|
|
|
| impedance) is used. |
|
|
|
|
|
|
|
| 2 | Overcurrent during | • | The deceleration time | is too short. | • | Increase the deceleration time | . |
|
| |
|
| deceleration |
| (During deceleration) |
|
|
|
|
|
|
|
| 3 | Overcurrent during | • | The load fluctuates abruptly. |
| • Reduce the load fluctuation. |
|
|
| ||
|
| operation | • | The load is in an abnormal condition. | • Check the load (operated machine). |
|
|
| |||
| 5 | Arm overcurrent at | • | A main circuit element is defective. | • Make a service call. |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| |
| 4 | Overcurrent (An | • | The insulation of the output main circuit or | • Check the cables and wires for defective |
| |||||
|
| overcurrent on the |
| motor is defective. |
|
| insulation. |
|
|
|
|
|
| load side at | • | The motor has too small impedance. |
|
|
|
|
|
| |
| A | Overvoltage during | • | The input voltage fluctuates abnormally. | • Insert a suitable input reactor. |
|
|
| |||
|
| acceleration | (1) The power supply has a capacity of |
|
|
|
|
|
| ||
|
|
|
| 200kVA or more. |
|
|
|
|
|
|
|
|
|
| (2) A power factor improvement capacitor is |
|
|
|
|
|
| ||
|
|
|
| opened or closed. |
|
|
|
|
|
|
|
|
|
| (3) A system using a thyristor is connected |
|
|
|
|
|
| ||
|
|
|
| to the same power distribution line. |
|
|
|
|
|
| |
|
|
| • A restart signal is input to the rotating | • | Use |
|
|
| |||
|
|
|
| motor after a momentary stop, etc. |
|
|
|
| |||
| B | Overvoltage during | • | The deceleration time | is too short. | • | Increase the deceleration time | . |
|
| |
|
| deceleration |
| (Regenerative energy is too large.) | • Install a suitable dynamic braking resistor. |
| |||||
|
|
| • | (dynamic braking resistor activa- | • | Enable | (dynamic braking selec- |
| |||
|
|
|
| tion) is off. |
|
| tion). |
|
|
|
|
|
|
| • | (overvoltage limit operation) is off. | • | Enable | (overvoltage limit opera- |
| |||
|
|
| • The input voltage fluctuates abnormally. |
| tion). |
|
|
|
| ||
|
|
| (1) The power supply has a capacity of | • Insert a suitable input reactor. |
|
|
| ||||
|
|
|
| 200kVA or more. |
|
|
|
|
|
|
|
|
|
| (2) A power factor improvement capacitor is |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| 13 | |||
|
|
|
| opened or closed. |
|
|
|
|
|
| |
|
|
| (3) A system using a thyristor is connected |
|
|
|
|
|
| ||
|
|
|
| to the same power distribution line. |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
(Continued overleaf)