■How to install

1

E6580757

How to install

■Installation location Danger

Do not install and operate the inverter if it is damaged or any component is missing. This can result in electric shock or fire. Please consult your local agency for repairs.

Prohibited

Must be installed in nonflammables such as metals.

The rear panel gets very hot so that if installation is in an inflammable object, this can result in fire.

Do not operate with the front panel cover removed. This can result in electric shock.

An emergency stop device must be installed that fits with system specifications (e.g. cuts off input

Mandatory

power then engages mechanical brakes).

 

Operation cannot be stopped immediately by the inverter alone, thus risking an accident or injury.

All options used must be those specified by Toshiba. The use of any other option may result in an acci- dent.

Ambient temperature of 40° C or less (model of 3.7kW or less) Warning

The main unit must be installed on a base that can bear the unit's weight.

If the unit is installed on a base that cannot withstand that weight, the unit may fall resulting in injury.

If braking is necessary (to hold motor shaft), install a mechanical brake. The brake on the inverter will

Mandatory

not function as a mechanical hold, and if used for that purpose, injury may result.

Installation location

Select a location with good indoor ventilation, place lengthwise in the vertical direction and attach to a metal wall surface.

If you are installing more than one inverter, the separation between inverters should be at least 5 centime- ters, and they should be arranged in horizontal rows.

If the inverters are horizontally arranged with no space between them (side-by-side installation), peel of the ventilation seals on top of the inverters and operate at 40° C or less (model of 3.7kW or less). Operate at 50° C or less (model of 5.5kW or more).

Standard installationHorizontal installation (side-by-side installation)

 

 

 

 

 

 

 

 

10 centimeters or

 

10 centimeters

 

 

 

 

 

or more

 

 

 

 

more

 

 

 

 

 

 

Remove seals on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VFS9

 

 

VFS9

VFS9

VFS9

top

5 centimeters

5 centimeters

 

 

 

 

 

 

or more

 

 

or more

 

 

 

 

 

 

 

 

Ambient temperature of 40° C or less (model of 3.7kW or less)

10 centimeters

 

or more

 

Ambient temperature of 50° C or less (model of 5.5kW or more).

 

 

 

 

 

The space shown in the diagram is the minimum allowable space. Because air cooled equipment has cooling fans built in on the top or bottom surfaces, make the space on top and bottom as large as possible to allow for air passage.

A-18

Page 29
Image 29
Toshiba VF-S9 How to install Danger, Installation location, Ambient temperature of 40 C or less model of 3.7kW or less