Toshiba VF-S9 Base frequency, Parameter setting, Upper limit, Lower-limit, The output frequency

Models: VF-S9

1 198
Download 198 pages 1.97 Kb
Page 73
Image 73
Upper limit

E6580757

Output frequency (Hz)

Upper limit

Output frequency (Hz)

Lower-limit

frequency

frequency

 

 

Frequency setting signal

Frequency setting signal

Frequencies that go

The output frequency

higher than

will

cannot be set at less

not be output.

 

than

.

■ Parameter setting

Title

Function

 

Adjustment range

Setting after setup

 

 

 

 

 

 

 

 

Upper limit frequency

0.5

(Hz)

50 or 60 *

 

 

Lower limit frequency

0.0

(Hz)

0.0

5

* Setting value depending on the end of Type – form.

 

 

AN, WN : 60Hz, WP : 50Hz

5.11Base frequency

Lower-limit : Base frequency 1

Function

Sets the base frequency in conformance with load specifications or the motor's rated frequency.

Note:This is an important parameter that determines the constant torque control area.

 

Base frequency voltage

 

 

 

 

Output voltage [V]

 

 

 

 

 

Output frequency (Hz)

 

 

 

 

 

 

Title

Function

Adjustment range

 

Setting after setup

 

 

 

 

 

Base frequency 1

25 400 (Hz)

 

50 or 60 *

 

 

 

 

 

*Setting value depending on the end of Type – form. AN, WN : 60Hz, WP : 50Hz