6.10 Preset-speed operation frequency 8 to 15
∼ : Preset-speed operation frequency 8 to 15
See Section 5.15 for details.
6.11 PWM carrier frequency
|
| : PWM carrier frequency |
|
| : Random mode |
| • Function | |
| 1) | The F300 parameter allows the tone of the magnetic noise from the motor to be changed by switching |
|
| the PWM carrier frequency. This parameter is also effective in preventing the motor from resonating |
|
| with its load machine or its fan cover. |
6 |
| |
2) | In addition, the F300 parameter reduces the electromagnetic noise generated by the inverter. Reduce | |
| the carrier frequency to reduce electromagnetic noise. Note: Although the electromagnetic noise level | |
|
| is reduced, the magnetic noise of the motor is increased. |
| 3) | The random mode reduces motor electromagnetic noise by changing the pattern of the reduced carrier |
|
| frequency. (Allowable operation frequency: 80Hz max.) |
[Parameter setting]
Title | Function | Adjustment range | Default setting |
|
|
|
|
| PWM carrier frequency | 2.0 ∼ 16.5 (kHz) * | 12.0 |
| Random mode | 0: Disabled, 1: Enabled | 0 |
*Load reduction will be required if the PWM carrier frequency is modified for each applicable motor model.
Load reduction ratios required [200V Class]
VFS9- |
| Carrier frequency |
| |
VFS9S- | 4kHz or less | 12kHz | 15kHz | 16.5kHz |
|
|
|
|
|
2002PL/M | 1.5A | 1.5A | 1.5A | 1.5A |
2004PL/M | 3.3A | 3.3A | 3.1A | 3.0A |
2007PL/M | 4.8A | 4.4A | 4.2A | 3.9A |
2015PL/M | 7.8A | 7.5A | 7.2A | 7.1A |
2022PL/M | 11.0A | 10.0A | 9.1A | 8.7A |
2037PM | 17.5A | 16.5A | 15.0A | 14.3A |
2055PL | 27.5A | 25.0A | 25.0A | 25.0A |
2075PL | 33.0A | 33.0A | 29.8A | 28.2A |
2110PM | 54.0A | 49.0A | 49.0A | 49.0A |
2150PM | 66.0A | 60.0A | 54.0A | 51.0A |