E6580757

This function will be displayed as during reading on the right. This previous setting is displayed. Ex.

cannot be set during the inverter operating. Always stop the inverter first and then program.

[Setting values]

Default setting

Setting to will return all parameters to the standard values that were programmed at the factory.

When 3 is programmed, will be displayed for a short time after setting and will then be erased

and displayed the original indication ( setup parameter). Trip history data will be cleared at this time. For setting setup parameters, see 4.1.4.

Trip clear

Setting to initializes the past four sets of recorded error history data.

(The parameter does not change.)

Cumulative operation time clear

5

Setting

to allows the initial resetting of the cumulative operation time monitor (0 [zero] time).

Initialize inverter type information

Setting to clears the trips when an format error occurs. But if the displayed, call us.

5.8Selecting forward and reverse runs (operation panel only)

: Forward/reverse run selection

Function

Program the direction of rotation when the running and stopping are made using the RUN key and STOP

key on the operation panel. Valid when

(command mode) is set to 1 (operation panel).

Parameter setting

Title

Function

Adjustment range

Default setting

 

 

 

 

 

Forward/reverse run selection

0: Forward run 1: Reverse run

0

Check the direction of rotation on the status monitor.

: Forward run

: Reverse run For monitoring, see 8.1.

When the F and R terminals are used for switching between forward and reverse rotation from the ter-

minal board, the forward/reverse run selection is rendered invalid. Short across the F-CC terminals: forward rotation

E-11