■Operations

 

 

 

 

 

 

E6580757

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

Danger

See item

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical construction work must be done by a qualified expert.

2.1

 

 

 

 

 

 

Connection of input power by someone who does not have that expert knowledge may re-

 

 

 

 

 

 

 

sult in fire or electric shock.

 

 

 

 

 

 

Connect output terminals (motor side) correctly.

2.1

 

 

 

 

 

 

If the phase sequence is incorrect, the motor will operate in reverse and that may result in

 

 

 

 

 

 

 

injury.

 

 

 

 

 

 

Wiring must be done after installation.

2.1

 

 

 

 

 

 

If wiring is done prior to installation that may result in injury or electric shock.

 

 

 

 

 

 

The following steps must be performed before wiring.

2.1

 

 

 

 

Mandatory

 

(1) Turn off all input power.

 

 

 

 

 

 

(2) Wait at least ten minutes and check to make sure that the charge lamp is no longer lit.

 

 

 

 

 

 

 

(3) Use a tester that can measure DC voltage (800VDC or more), and check to make sure

 

 

 

 

 

 

 

that the voltage to the DC main circuits (across PA-PC) is 45V or less.

 

 

 

 

 

 

 

If these steps are not properly performed, the wiring will cause electric shock.

 

 

 

 

 

 

Tighten the screws on the terminal board to specified torque.

2.1

 

 

 

 

 

 

If the screws are not tightened to the specified torque, it may lead to fire.

 

 

 

 

 

 

Check to make sure that the input power voltage is +10%, -15% of the rated power volt-

1.4.4

 

 

 

 

 

 

age written on the rating label (± 10% when the load is 100% in continuous operation)

 

 

 

 

 

 

 

If the input power voltage is not +10%, -15% of the rated power voltage (± 10% when the

 

 

 

 

 

 

 

load is 100% in continuous operation) this may result in fire.

 

 

 

 

 

 

Ground must be connected securely.

2.1

 

 

 

 

 

 

If the ground is not securely connected, it could lead to electric shock or fire when a mal-

2.2

 

 

 

 

Be Grounded

 

function or current leak occurs.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Warning

See item

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not attach equipment (such as noise filters or surge absorbers) that have built-in ca-

2.1

 

 

 

 

 

 

pacitors to the output (motor side) terminals.

 

 

 

 

 

Prohibited

 

That could result in a fire.

 

 

Operations

 

Danger

See item

 

Do not touch inverter terminals when electrical power is going to the inverter even if the

3.

 

motor is stopped.

 

 

Touching the inverter terminals while power is connected to it may result in electric shock.

 

 

Do not touch switches when the hands are wet and do not try to clean the inverter with a

3.

Prohibited

damp cloth. Such practices may result in electric shock.

 

Do not go near the motor in alarm-stop status when the retry function is selected.

3.

 

 

The motor may suddenly restart and that could result in injury.

 

 

Take measures for safety, e.g. attaching a cover to the motor, against accidents when the

 

 

motor unexpectedly restarts..

 

 

Turn input power on after attaching the front cover.

3.

 

When storing inside the cabinet and using with the front cover removed, always close the

 

 

cabinet doors first and then turn power on. If the power is turned on with the front cover or

 

Mandatory

the cabinet doors open, it may result in electric shock.

 

Make sure that operation signals are off before resetting the inverter after malfunction.

3.

 

If the inverter is reset before turning off the operating signal, the motor may restart sud-

 

 

denly causing injury.

 