E6580757

1) Standby on when ST is on

Motor speed

 

Coast stop

Use this setting if an ST (standby)

 

terminal is required.

 

 

 

 

* The ST terminal is not assigned

 

 

as standard default setting.

F-CC

 

Assign the ST function to an

 

idle input terminal by the input

ST-CC

 

terminal selection.

 

 

2) Standby always on (Default setting)

The inverter enters a standby status, irrespective of the ST signal status. Motor rotation stops according to the selected deceleration time at the set frequency.

3) Interlocked with F/R

Motor speed

 

Coast stop

 

 

Turning the operation

 

 

signal (F/R) off causes

 

 

the motor to coast to a

 

 

6

 

stop.

F-CC

 

4) Standby on when ST is off

Inversion of item 1) above.

6.2.2Setting the reset signal

: RST (reset) signal selection

Function

 

The

parameter specifies reset function activation timing, depending on the particular status of

the RST (reset) signal.

1)

Standard setting (reset on when RST-CC on to off)

2)

Activated by turning RST off (reset on when RST-CC off to on)

This parameter is available in the modifying input terminal functions () = 10 (RST).

To reset the protective function on the parameter setting , do any of the following.

1.Turn off the power.

2.Press the STOP key twice while the protection function is displayed.

3.Turn on and off the error reset control input signal.

F-5