■Selection of wiring devices

E6580757

Selection of wiring devices

 

 

 

Non-fuse circuit

Magnetic contactor

Overload relay

Earth leakage

 

Capacity of

 

breaker

(MC)

(THR)

 

breaker

Voltage class

applicable

Inverter model

(MCCB)

 

 

 

 

(ELCB)

motor

Rated

Type

Rated

Type

Adjusted current

Type

Rated

Type

 

 

 

(kW)

 

current

Note1)

current

Note1)

(A)

Note1)

current

Note1)

 

 

 

(A)

 

(A)

 

(For reference)

 

(A)

 

 

 

 

 

 

 

 

 

 

 

 

 

0.2

VFS9S-2002PL

10

NJ30N

11

C11J

1.3

T13J

10

NJV50E

Single-phase

0.4

VFS9S-2004PL

15

NJ30N

11

C11J

2.3

T13J

15

NJV50E

0.75

VFS9S-2007PL

20

NJ30N

11

C11J

3.6

T13J

20

NJV50E

200V class

1.5

VFS9S-2015PL

30

NJ30N

18

C20J

6.8

T13J

30

NJV50E

 

 

2.2

VFS9S-2022PL

40

NJ50E

35

C35J

9.3

T13J

40

NJV50E

 

0.2

VFS9-2002PM

5

NJ30N

11

C11J

1.3

T13J

5

NJV50E

 

0.4

VFS9-2004PM

5

NJ30N

11

C11J

2.3

T13J

5

NJV50E

 

0.75

VFS9-2007PM

10

NJ30N

11

C11J

3.6

T13J

10

NJV50E

Three-phase

1.5

VFS9-2015PM

15

NJ30N

11

C11J

6.8

T13J

15

NJV50E

2.2

VFS9-2022PM

20

NJ30N

13

C13J

9.3

T13J

20

NJV50E

200V class

3.7

VFS9-2037PM

30

NJ30N

26

C25J

15

T20J

30

NJV50E

 

5.5

VFS9-2055PL

50

NJ50E

35

C35J

22

T35J

50

NJV50E

 

7.5

VFS9-2075PL

60

EJ100F

50

C50J

28

T35J

60

NJV60F

 

11

VFS9-2110PM

100

EJ100F

65

C65J

44

T65J

100

NJV100F

 

15

VFS9-2150PM

125

EJ225F

80

C80A

57

T65J

125

NJV225F

 

0.75

VFS9-4007PL

5

NJ30N

9

C11J

1.6

T13J

5

NJV50E

 

1.5

VFS9-4015PL

10

NJ30N

9

C11J

3.6

T13J

10

NJV50E

Three-phase

2.2

VFS9-4022PL

15

NJ30N

9

C11J

5.0

T13J

15

NJV50E

3.7

VFS9-4037PL

20

NJ30N

13

C13J

6.8

T13J

20

NJV50E

400V class

5.5

VFS9-4055PL

30

NJ30N

17

C20J

11

T13J

30

NJV50E

 

7.5

VFS9-4075PL

30

NJ30N

25

C25J

15

T20J

30

NJV50E

 

11

VFS9-4110PL

50

EJ50E

33

C35J

22

T35J

50

NJV50E

 

15

VFS9-4150PL

60

EJ100F

48

C50J

28

T35J

60

NJV100F

Note 1: Produced by Schneider Toshiba electric corporation.

Note 2: Be sure to attach a surge killer to the exciting coil of the relay and the magnetic contactor. Selection of surge killers for Toshiba magnetic contactors

200V class: Surge absorbing units are optionally available for Toshiba C11J to C65J, or Model SS-2 for C50J and C65J

400V class: For the operation and control circuits, regulate the voltage at 200V or less with a step-down

 

 

transformer.

 

 

 

 

10

 

 

 

 

 

Note 3: When using the auxiliary contacts 2a of the magnetic contactor MC for the control circuit, connect the

 

 

 

 

contacts 2a in parallel to increase reliability.

 

 

 

 

 

 

 

Of the wiring devices listed in the above table, the magnetic contactors (MC) and the overload relays (Th-Ry) are

 

 

intended for use with the Mighty J series. When using the old series (ESPER Mighty series), refer to the table

 

 

below showing the correspondence between the two series.

 

 

 

 

 

 

 

 

 

 

 

Magnetic contactor (MC)

 

Overload relay

 

 

ESPER Mighty series

 

Mighty J series

 

ESPER Mighty series

Mighty J series

 

 

 

 

 

 

 

 

C12A

 

C13J

 

T11A

T13J

 

 

C20A

 

C20J

 

T20A

T20J

 

 

C35A

 

C35J

 

T35A

T35J

 

 

C50A

 

C50J

 

T65A

T65J

 

 

C65A

 

C65J

 

 

 

J-2