E6580757

2)Preset-speed frequency setting

Set the speed (frequency) of the number of steps necessary.

Setting from speed 1 to speed 7

Title

 

 

 

 

 

 

 

 

Function

 

 

 

 

Adjustment range

 

 

Default setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Preset-speed operation frequencies

 

 

 

 

 

 

 

 

 

 

 

 

 

or

 

 

 

 

(Hz)

 

 

 

 

 

0.0

 

 

 

 

 

 

1~7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

~

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting from speed 8 to speed 15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Title

 

 

 

 

 

 

 

Function

 

 

 

 

Adjustment range

 

 

Default setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Preset-speed frequencies 8~15

 

 

 

(Hz)

 

 

 

 

 

0.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Examples of preset-speed contact input signals (JP301 set to sink logic)

 

 

 

 

 

 

 

 

 

 

 

O: ON -: OFF (Speed commands other than preset-speed commands are valid when all are OFF)

 

 

 

 

CC

Terminal

 

 

 

 

 

 

 

 

 

 

Preset-speed

 

 

 

 

 

 

 

 

 

S1

 

1

 

2

 

3

4

5

6

 

7

8

9

 

10

11

12

13

14

15

 

 

 

 

 

 

 

 

 

 

 

 

S2

S1-CC

 

{

-

 

{

-

{

-

 

{

-

{

-

{

-

 

{

-

{

 

5

S2-CC

 

-

 

{

{

-

-

{

{

-

-

 

{

{

-

 

-

{

{

 

S3

 

 

 

 

 

S3-CC

 

-

 

-

 

-

{

{

{

{

-

-

 

-

-

{

{

{

{

 

 

RST

 

 

 

 

 

 

RST-CC

 

-

 

-

 

-

-

-

-

 

-

{

{

 

{

{

{

{

{

{

 

 

 

 

 

 

 

 

 

 

Terminal functions are as follows.

Terminal S1

Input terminal function selection 4

(S1)

=6 (SS1)

Terminal S2

Input terminal function selection 5 (S2)

=7 (SS2)

Terminal S3

Input terminal function selection 6 (S3)

=8 (SS3)

Terminal RST

Input terminal function selection 3

(RST)

=9 (SS4)

SS4 is not allocated to standard default setting. Use the input terminal function selection to allocate SS4 an idle terminal. In the above example the RST terminal is used for SS4.

Example of a connection diagram (JP301 set to sink logic)

VF-S9

 

F (Forward run)

Forward

 

R (Reverse run)

Reverse

CC

 

S1

Preset-speed 1

 

S2

Preset-speed 2

S3

Preset-speed 3

RST

Preset-speed 4

E-23

Page 83
Image 83
Toshiba VF-S9 manual Preset-speed, S3-CC, Terminal functions are as follows Terminal S1, =6 SS1