Toshiba VF-S9 manual Auto-restart after momentary power failure Auto-restart function

Models: VF-S9

1 198
Download 198 pages 1.97 Kb
Page 108
Image 108
1)Auto-restart after momentary power failure (Auto-restart function)

 

 

 

 

E6580757

 

 

 

 

 

 

 

 

 

 

 

 

 

Title

Function

Adjustment range

Default setting

 

 

 

 

 

 

 

 

 

0: Disabled

 

 

 

 

 

1: At auto-restart after momentary stop

 

 

 

 

 

2: When turning ST-CC on or off

 

 

 

 

Auto-restart control

3: At auto-restart or when turning ST-CC on or off

 

 

 

 

4: Motion of DC braking at start-up (at auto-

0

 

 

 

selection

restart after momentary stop)

 

 

 

 

 

 

 

 

5: Motion of DC braking at start-up (when turning

 

 

 

 

 

ST-CC on or off)

 

 

 

 

 

6: Motion of DC braking at start-up (at auto-

 

 

 

 

 

restart or when turning ST-CC on or off)

 

 

*If the motor is restarted in retry mode, this function will operate, regardless of the setting of this parameter.

1)Auto-restart after momentary power failure (Auto-restart function)

Input voltage

Motor speed

F-CC

6 Setting Input voltage to 2) Restarting motor during coasting (Motor speed search function), (Motor speed): This function operates after power has been restored following detection of an undervoltage by the main circuits and control power.

2) Restarting motor during coasting (Motor speed search function)

Motor speed

F-CC

ST-CC

Setting 3)DC braking during restart to Manual background, (Manual background): This function operates after the ST-CC terminal connection has been opened first and then connected again.

3)DC braking during restart

If this parameter is set to either " Manual background ", " Manual background ", or " Manual background ", DC braking specified by parameter Manual background, or Manual background will be conducted during the restart of the motor.

This function is effective when the motor is under a momentary power failure or coasting status and is re- versing for some external reason.

F-24

Page 108
Image 108
Toshiba VF-S9 manual Auto-restart after momentary power failure Auto-restart function, DC braking during restart