6.5Frequency priority selection

E6580757

6.5Frequency priority selection

6.5.1Using a frequency command according to the particular situation

6.5.1Using a frequency command according to the particular situation : Frequency setting mode selection : Frequency priority selection

Function

Use the above parameters to select the command to be used for frequency setting, and to assign priority to one of the two types of input frequency reference signals.

Combination of the  : Frequency setting mode selection : Frequency priority selection and 1) Automatic frequency switching 1 parameters

Switching via terminal board input

Parameter setting

Title

Function

Adjustment range

Default setting

 

 

 

 

 

 

0: Terminal board

 

 

Frequency setting mode selection

1: Operation panel

2

 

 

2: Internal potentiometer

 

6

Parameter setting

Title

Function

Adjustment range

Default setting

 

 

 

 

 

 

0: VIA/II, VIB

 

 

 

1: VIB, VIA/II

 

 

 

2: External switching

 

 

 

(FCHG enabled)

 

 

Frequency priority selection

3: External contact UP/DOWN

0

 

 

4: External contact UP/DOWN

 

 

 

(Setting retained even if the

 

 

 

power is turned off)

 

 

 

5: VIA/II + VIB

 

The VIA terminal and II terminal cannot be used at the same time.

1) Automatic frequency switching 1

Frequency priority selection parameter Manual background (Default setting)

Manual background = 0: Terminal board is selected.

First priority is assigned to analog input terminals VIA/II, and second priority to analog input terminals VIB. When the input to VIA/II with first priority becomes null, control will be switched automatically to VIB with sec- ond priority.

F-11