Table of output terminal functions (2/2)

Function

Code

Function

 

Action

 

 

 

No.

 

 

 

 

 

 

 

 

15

RUNN

Inversion of RUN/STOP

Inversion of RUN setting

 

 

 

 

16

POL

OL pre-alarm

ON: 50% or more of calculated value of overload

 

 

 

protection level

 

 

 

 

 

 

 

OFF: Less than 50% of calculated value of over-

 

 

 

load protection level

 

 

 

 

17

POLN

Inversion of OL pre-alarm

Inversion of POL setting

 

 

 

 

18

POHR

Braking resistor overload pre-alarm

ON: 50% or more of calculated value of

set

 

 

 

overload protection level

 

 

 

 

 

 

OFF: Less than 50% of calculated value of

 

 

 

set overload protection level

 

 

19

POHRN

Inversion of braking resistor overload pre-alarm

Inversion of POHR setting

 

 

 

20

POT

Over-torque detection pre-alarm

ON: Torque current is equal to or larger than 70%

 

 

 

of

set value.

 

 

 

 

 

 

 

OFF: Torque current is smaller than 70% of

 

 

 

set value.

 

 

 

 

21

POTN

Inversion of over-torque detection pre-alarm

Inversion of POT setting

 

 

 

 

22

PAL

Pre-alarm

ON: When POL, POHR or POT is on, or

, or

 

 

 

issues an alarm

 

 

 

 

 

 

 

OFF: When POL, POHR and POT are off, and ,

 

 

 

and

issue no alarm

 

 

 

23

PALN

Inversion of pre-alarm

Inversion of PAL setting

 

 

 

 

24

UC

Low-current detection

ON: Output current is equal to or larger than

 

 

 

set value and longer than

set time.

 

 

 

OFF: Output current is smaller than

set

 

 

 

value.

 

 

 

 

 

25

UCN

Inversion of low-current detection

Inversion of UC setting

 

 

 

 

26

HFL

Hard fault

ON: Tripping (

,

,

,

,

,

 

 

 

,

,

 

,

,

,

 

 

 

,

)

 

 

 

 

 

 

 

OFF: Failure other than the above

 

 

27

HFLN

Inversion of hard fault

Inversion of HFL setting

 

 

 

 

28

LFL

Soft fault

ON: Tripping (

,

 

,

,

,

 

 

 

,

)

 

 

 

 

 

 

 

OFF: Failure other than the above

 

 

29

LFLN

Inversion of soft fault

Inversion of LFL setting

 

 

 

 

11

K-11

Page 178
Image 178