E6580757
■Table of output terminal functions (2/2)
Function | Code | Function |
| Action |
|
|
| |
No. |
|
|
|
|
|
|
|
|
15 | RUNN | Inversion of RUN/STOP | Inversion of RUN setting |
|
|
|
| |
16 | POL | OL | ON: 50% or more of calculated value of overload | |||||
|
|
| protection level |
|
|
|
| |
|
|
| OFF: Less than 50% of calculated value of over- | |||||
|
|
| load protection level |
|
|
|
| |
17 | POLN | Inversion of OL | Inversion of POL setting |
|
|
|
| |
18 | POHR | Braking resistor overload | ON: 50% or more of calculated value of | set | ||||
|
|
| overload protection level |
|
|
| ||
|
|
| OFF: Less than 50% of calculated value of | |||||
|
|
| set overload protection level |
|
| |||
19 | POHRN | Inversion of braking resistor overload | Inversion of POHR setting |
|
|
| ||
20 | POT | ON: Torque current is equal to or larger than 70% | ||||||
|
|
| of | set value. |
|
|
|
|
|
|
| OFF: Torque current is smaller than 70% of | |||||
|
|
| set value. |
|
|
|
| |
21 | POTN | Inversion of | Inversion of POT setting |
|
|
|
| |
22 | PAL | ON: When POL, POHR or POT is on, or | , or | |||||
|
|
| issues an alarm |
|
|
|
| |
|
|
| OFF: When POL, POHR and POT are off, and , | |||||
|
|
| and | issue no alarm |
|
|
| |
23 | PALN | Inversion of | Inversion of PAL setting |
|
|
|
| |
24 | UC | ON: Output current is equal to or larger than | ||||||
|
|
| set value and longer than | set time. | ||||
|
|
| OFF: Output current is smaller than | set | ||||
|
|
| value. |
|
|
|
|
|
25 | UCN | Inversion of | Inversion of UC setting |
|
|
|
| |
26 | HFL | Hard fault | ON: Tripping ( | , | , | , | , | , |
|
|
| , | , |
| , | , | , |
|
|
| , | ) |
|
|
|
|
|
|
| OFF: Failure other than the above |
|
| |||
27 | HFLN | Inversion of hard fault | Inversion of HFL setting |
|
|
|
| |
28 | LFL | Soft fault | ON: Tripping ( | , |
| , | , | , |
|
|
| , | ) |
|
|
|
|
|
|
| OFF: Failure other than the above |
|
| |||
29 | LFLN | Inversion of soft fault | Inversion of LFL setting |
|
|
|
|
11