E6580757

2) Inverter over load characteristics

Set to protect the inverter unit. Cannot be changed or turned off by parameter setting.

If the inverter overload trip function ( ) is activated frequently, this can be improved by adjusting the

stall operation level downward or increasing the acceleration time or deceleration time .

Inverter overload

Time [s]

100%: inverter rated output current

 

 

 

Output current [%]

 

 

 

 

5

 

 

* To protect the inverter, overload trip may activate in a short period of time when output

 

 

 

current reaches 150% or higher.

 

 

 

Inverter overload protection characteristics

 

 

5.15 Preset-speed operation (speeds in 15 steps)

 

 

 

 

 

 

: Preset-speed operation frequencies 1~7

~

: Same as Sr1 ~ Sr7

 

 

: Preset-speed operation frequencies 8~15

Function

A maximum of 15 speed steps can be selected just by switching an external contact signal. Multi-speed

frequencies can be programmed anywhere from the lower limit frequency to the upper limit frequency

.

[Setting method]

1)Run/stop

The starting and stopping control is done from the terminal board.

Title

Function

Adjustment range

Setting

 

 

 

 

 

Command mode selection

0: Terminal board

1

 

1: Operation panel

 

 

 

Note:If speed commands (analog signal or digital input) are switched in line with preset-speed operations, select

the terminal board using the frequency setting mode selection .

See 3) or 5.5

E-22

Page 82
Image 82
Toshiba VF-S9 manual Preset-speed operation speeds in 15 steps, Inverter over load characteristics, Same as Sr1 ~ Sr7