2) Inverter over load characteristics
Set to protect the inverter unit. Cannot be changed or turned off by parameter setting.
If the inverter overload trip function ( ) is activated frequently, this can be improved by adjusting the
stall operation level downward or increasing the acceleration time or deceleration time .
Inverter overload
Time [s]
100%: inverter rated output current
|
|
| Output current [%] |
|
|
|
|
5 |
|
| * To protect the inverter, overload trip may activate in a short period of time when output |
|
|
| current reaches 150% or higher. |
|
|
| Inverter overload protection characteristics |
|
| 5.15 | |
|
|
|
|
|
| ∼ | : |
~ | : Same as Sr1 ~ Sr7 | ||
|
| ∼ | : |
• Function
A maximum of 15 speed steps can be selected just by switching an external contact signal.
frequencies can be programmed anywhere from the lower limit frequency to the upper limit frequency
.
[Setting method]
1)Run/stop
The starting and stopping control is done from the terminal board.
Title | Function | Adjustment range | Setting |
|
|
|
|
| Command mode selection | 0: Terminal board | 1 |
| 1: Operation panel | ||
|
|
|
Note:If speed commands (analog signal or digital input) are switched in line with
the terminal board using the frequency setting mode selection . | ⇒ See 3) or 5.5 |