Toshiba VF-S9 manual Remedies, E ffects of leak current across lines, Inverter

Models: VF-S9

1 198
Download 198 pages 1.97 Kb
Page 25
Image 25
Inverter

E6580757

Power

ELCB

Inverter

 

supply

 

 

 

ELCB

Inverter

 

 

1

Leak current path across ground

Remedies:

M

M

1.Reduce PWM carrier frequency.

The setting of PWM carrier frequency is done with the parameter Remedies: .

2.Use high frequency remedial products (Schneider Toshiba electric corporation: Esper Mighty Series) for earth leakage breakers. If you use equipment like this, there is no need to reduce the PWM carrier frequency.

3.If the sensors and CRT are affected, it can be remedied using the reduction of PWM carrier frequency described in 1 above, but if this cannot be remedied since there is an increase in the motor's magnetic noise, please consult with Toshiba.

(2) E ffects of leak current across lines

Power supply

Inverter

Thermal relay

CT

M

Leak current path across wires

A

(1)Thermal relays

The high frequency component of current leaking into electrostatic capacity between inverter out- put wires will increase the effective current values and make externally connected thermal relays operate improperly. If the wires are more than 50 meters long, it will be easy for the external ther- mal relay to operate improperly with models having motors of low rated current (several A(ampere) or less), especially the 400V class low capacity (3.7kW) models, because the leak cur- rent will increase in proportion to the motor rating.

A-14

Page 25
Image 25
Toshiba VF-S9 manual Remedies, E ffects of leak current across lines, Inverter