Toshiba VF-S9 manual Setting frequency command characteristics, Parameter setting

Models: VF-S9

1 198
Download 198 pages 1.97 Kb
Page 97
Image 97
6.5.2Setting frequency command characteristics

E6580757

6.5.2Setting frequency command characteristics

: VIA/II input point 1 setting

: VIA/II input point 1 frequency

: VIA/II input point 2 setting

: VIA/II input point 2 frequency

: VIB input point 1 setting (Frequency UP response time)

: VIB input point 1 frequency (Frequency UP step width)

: VIB input point 2 setting (Frequency DOWN response time)

: VIB input point 2 frequency (Frequency DOWN step width)

Function

6

 

These parameters adjust the output frequency according to the externally applied analog signal (0-10V dc voltage, 4-20mA dc current) and the entered command for setting an external contact frequency.

Parameter setting

Title

Function

 

 

 

Adjustment range

Default setting

 

 

 

 

 

 

 

VIA/II input point 1 setting

0

100

(%)

0

 

VIA/II input point 1 frequency

0.0

400.0 (Hz)

0.0

 

VIA/II input point 2 setting

0

100

(%)

100

 

VIA/II input point 2 frequency

0.0

400.0 (Hz)

50 or 60 *1

 

VIB input point 1 setting

0

100

(%)

0

 

Frequency UP response time

0

100

(1: 0.1 s)

0

 

 

VIB input point 1 frequency

0.0

400.0 (Hz)

0.0

 

Frequency UP step width

0.0

400.0

0

 

VIB input point 2 setting

0

100

(%)

100

 

Frequency DOWN response time

0

100

(1: 0.1 s)

100

 

VIB input point 2 frequency

0.0

400.0 (Hz)

50 or 60 *1

 

Frequency DOWN step width

0.0

400.0

50 or 60 *1

Note1)

Setting value of

and

depending on the end of Type form. AN, WN : 60Hz, WP: 50Hz.

Note2)

~

can be used as UP/DOWN function depend on the setting.

Note3)

Don't set the same value between point 1 and point 2.

 

If set the same value, the

is displayed.

F-13

Page 97
Image 97
Toshiba VF-S9 manual Setting frequency command characteristics, VIA/II input point 1 setting VIA/II input point 1 frequency