■Replacement of expendable parts

E6580757

(Note) Before an insulation test, always disconnect all cables from the main circuit terminal board and test the inverter separately from other equipment.

500V insulation tester (megger)

7.Never test the inverter for pressure. A pressure test may cause damage to its components.

8.Voltage and temperature check Recommended voltmeter:

Input side ... Moving-iron type voltmeter (Manual background)

Output side ... Rectifier type voltmeter (Manual background)

It will be very helpful for detecting a defect if you always measure and record the ambient temperature before, during and after the operation.

Replacement of expendable parts

The inverter is composed of a large number of electronic parts including semiconductor devices. The fol- lowing parts deteriorate with the passage of time because of their composition or physical properties. The use of aged or deteriorated parts leads to degradation in the performance or a breakdown of the inverter. To avoid such trouble, the inverter should be checked periodically.

Note) Generally, the life of a part depends on the ambient temperature and the conditions of use. The life spans listed below are applicable to parts when used under normal environmental conditions.

1) Cooling fan

The fan, which cools down heat-generating parts, has a service life of about 30,000 hours (about 2 or 3 years of continuous operation). The fan also needs to be replaced if it makes a noise or vibrates ab- normally.

2) Smoothing capacitor

The smoothing aluminum electrolytic capacitor in the main circuit DC section degrades in performance

 

because of ripple currents, etc. It becomes necessary to replace the capacitor after it is used for about

 

14

5 years under normal conditions. If your inverter is intended for a 3.7kW or smaller motor, replace the

 

smoothing capacitor together with the printed circuit board on which it is mounted.

 

 

<Criteria for appearance check>

 

Absence of liquid leak

 

Safety valve in the depressed position

 

Measurement of electrostatic capacitance and insulation resistance

 

N-3