6.17 Communication function (Common serial)
: Data transfer speed
: Parity
: Inverter number
: Communication error trip time
Refer to the COMMUNICATIONS EQUIPMENT USER'S MANUAL for details.
| • | Function | |
|
| The VFS9 Series allows a data communication network to be constructed for exchanging data between | |
|
| a host computer or controller (referred to collectively as the computer) and the inverter by connecting an | |
|
| optional RS232C or RS485 communication conversion unit. | |
|
| ||
|
| The following functions are enabled by data communication between the computer and inverter | |
|
| (1) | Monitoring inverter status (such as the output frequency, current, and voltage) |
6 |
| ||
| (2) | Sending RUN, STOP and other control commands to the inverter | |
|
| (3) | Reading, editing and writing inverter parameter settings |
|
| <RS232C communication> | |
|
| Data can be exchanged between one computer and one inverter. | |
|
| <RS485 communication> | |
|
| Data can be exchanged between the computer and a maximum of 64 inverters. |
✩The following are available as common serial optional units:
•RS232C communications conversion unit (Model: RS2001Z)
Communications cable (Model: CAB0011, 1m long; CAB0013, 3m long; or CAB0015, 5m long)
•RS485 communication conversion unit with terminal board (Model: RS4001Z)
Communication cable (Model: CAB0011, 1m long; CAB0013, 3m long; or CAB0015, 5m long)
Note 1.: Limit the distance between the common serial optional units and the inverter to 5m.
2.: Set Data transfer speed to 9600 bps or less if data exchange between the common serial optional units and the inverter.