Toshiba VF-S9 manual Setting environmental protection, Setting parameters by operating method

Models: VF-S9

1 198
Download 198 pages 1.97 Kb
Page 65
Image 65
5.3Setting environmental protection

E6580757

5.3Setting environmental protection

: Automatic environment setting

Function

This automatically programs all parameters related to inverter environmental protection (auto-restart or ride-through control after momentary power failure, supply voltage correction, acceleration/deceleration S- pattern).

This parameter is especially suitable for wind force or hydraulic machinery such as fans and pumps Note: Do not use this parameter for equipment such as transporters, since it is dangerous to operate

automatically such equipment after temporary stops.

[Parameter setting]

Title

Function

Adjustment range

Default setting

 

 

 

 

 

 

 

 

Automatic environment setting

0: Disabled

0

 

 

 

1: Automatic setting

 

 

 

5

 

 

 

 

Values of automatically programmed parameters

 

 

 

 

 

 

 

Title

Function

 

Default setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto-restart control selection

1: At auto-restart after

0: Disabled

 

 

 

momentary stop

 

 

 

 

 

 

 

Regenerative power ride-through control

1: Enabled

0: Disabled

 

 

 

 

 

 

 

 

1: Supply voltage

1: Supply voltage cor-

 

Supply voltage correction

corrected, output volt-

rected, output voltage

 

 

 

age limited

limited

 

 

Acceleration/deceleration 1 pattern

1: S-pattern 1

0: Linear

 

 

 

 

 

 

 

5.4Setting parameters by operating method

: Automatic function setting

Function

Automatically programs all parameters (parameters described below) related to the functions by selecting the inverter's operating method.

The major functions can be programmed simply.

[Parameter setting]

Title

Function

Adjustment range

Default setting

 

 

 

 

 

 

0: Disabled

 

 

 

1: Coast stop

 

 

Automatic function setting

2: 3-wire operation

0

 

 

3: External input UP/DOWN setting

 

 

 

4: 4-20mA current input operation

 

E-5

Page 65
Image 65
Toshiba VF-S9 Setting environmental protection, Setting parameters by operating method, Automatic environment setting