Toshiba VF-S9 manual Standard default setting, Adjusting the meter in inverter stop state

Models: VF-S9

1 198
Download 198 pages 1.97 Kb
Page 70
Image 70
■Adjusting the meter in inverter stop state

E6580757

[Example of how to adjustment the FM terminal frequency meter]

*Use the meter's adjustment screw to pre-adjust zero-point.

 

 

Key operated

LED display

 

 

 

 

 

Operation

 

 

 

 

 

 

 

 

 

 

 

-

 

Displays the operation frequency. (When standard monitor display selec-

 

 

tion

is set to

[operation frequency]

 

 

 

 

 

 

 

 

 

 

 

 

Press the MON key to display the first basic parameter

(automatic

 

 

 

 

acceleration/deceleration) .

 

 

 

 

 

 

 

Press either the

key or the

key to select " ."

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the ENTER key to display the operation frequency.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the

key or the

key to adjust the meter. The meter reading will

 

 

 

 

change at this time but be careful because there will be no change in the

 

 

 

 

inverter's digital LED (monitor) indication.

 

 

 

 

 

 

 

 

 

 

 

[Hint]

 

 

 

 

 

 

 

 

 

 

 

It's easier to make the adjustment if

 

 

 

 

 

 

 

 

 

 

you push and hold for several seconds.

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

The adjustment is complete.

and the frequency are displayed alter-

 

 

 

 

nately.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The display returns to its original indications (displaying the operation

 

 

 

 

frequency). (When standard monitor display selection

 

 

 

 

 

 

is set to

[operation frequency].

 

 

Adjusting the meter in inverter stop state

If, when adjusting the meter for output current, there are large fluctuations in data during adjustment, making adjustment difficult, the meter can be adjusted in inverter stop state.

When setting 5.7Standard default setting to  : Default setting for adjustment (100% fixed current), a signal of absolute values will be output

(inverter's rated current = 100%). In this state, adjust the meter with the Manual background (Meter adjustment) parameter.

After meter adjustment is ended, set Manual background to Manual background (output current).

5.7Standard default setting

Manual background : Default setting

Function

 

 

 

Allows setting of all parameters to the standard default setting, etc. at one time.

 

 

 

 

 

Title

Function

Adjustment range

Default setting

 

 

 

 

 

 

 

 

0 2 : - (invalid)

 

 

 

Standard setting mode selection

3: Default setting

0

 

 

4: Trip clear

 

 

 

5: Cumulative operation time clear

 

 

 

 

6: Initialize inverter type information

 

E-10

Page 70
Image 70
Toshiba VF-S9 manual Standard default setting, Adjusting the meter in inverter stop state, Default setting