Error code

Communication

No.

Problem

Possible causes

Remedies

 

 

 

C

Overvoltage during

The input voltage fluctuates abnormally.

Insert a suitable input reactor.

 

 

 

 

 

constant-speed op-

(1) The power supply has a capacity of

 

 

 

 

 

 

 

 

 

eration

 

200kVA or more.

 

 

 

 

 

 

 

 

 

 

 

(2) A power factor improvement capacitor is

 

 

 

 

 

 

 

 

 

 

 

opened or closed.

 

 

 

 

 

 

 

 

 

 

 

(3) A system using a thyristor is connected

 

 

 

 

 

 

 

 

 

 

 

to the same power distribution line.

 

 

 

 

 

 

 

 

 

 

The motor is in a regenerative state be-

Install a dynamic braking resistor.

 

 

 

 

 

 

cause the load causes the motor to run at

 

 

 

 

 

 

 

 

 

 

 

a frequency higher than the inverter out-

 

 

 

 

 

 

 

 

 

 

 

put frequency.

 

 

 

 

 

 

 

 

 

D

Inverter overload

The acceleration time

is too short.

Increase the acceleration time

.

 

 

 

 

 

The DC braking amount is too large.

Reduce the DC braking amount

 

 

 

 

 

 

The V/F setting is improper.

 

 

and the DC braking time

 

.

 

 

 

 

 

A restart signal is input to the rotating

Check the V/F parameter setting.

 

 

 

 

 

 

motor after a momentary stop, etc.

Use

(auto-restart) and

 

 

 

 

 

 

The load is too large.

 

 

(ride-through control).

 

 

 

 

 

 

 

 

 

 

Use an inverter with a larger rating.

 

 

 

E

Motor overload

The V/F setting is improper.

 

Check the V/F parameter setting.

 

 

 

 

 

The motor is locked up.

 

Check the load (operated machine).

 

 

 

 

 

Low-speed operation is performed con-

Adjust

to the overload that the

 

 

 

 

 

 

tinuously.

 

 

motor can withstand during operation in a

 

 

 

 

 

An excessive load is applied to the motor

 

low speed range.

 

 

 

 

 

 

 

 

during operation.

 

 

 

 

 

 

 

 

*

9

Output phase failure

A phase failure occurred in the output line

Check the main circuit output line, motor,

 

 

 

 

 

 

of the main circuit.

 

 

etc., for phase failure.

 

 

 

 

 

 

 

 

 

 

Enable

(Output phase failure de-

 

 

 

 

 

 

 

 

 

tection).

 

 

 

 

 

*

8

Input phase failure

A phase failure occurred in the input line

Check the main circuit input line for phase

 

 

 

 

 

 

of the main circuit.

 

 

failure.

 

 

 

 

 

 

 

 

 

 

 

Enable

(input phase failure detec-

 

 

 

 

 

 

 

 

 

tion).

 

 

 

 

 

 

2Eh

External thermal trip

A thermal trip command is entered from

Check the external input device.

 

 

 

 

 

 

 

an external input device.

 

 

 

 

 

 

 

 

*

20h

Over-torque trip

The load torque rises up to the over-

Enable

(Over - torque trip selection)

 

 

 

 

 

 

torque detection level during operation

Check whether the system is in a normal

 

 

 

 

 

 

 

 

 

condition.

 

 

 

 

 

 

F

Dynamic braking re-

The deceleration time is too short.

Increase the deceleration time

.

 

 

 

 

sistor overload trip

The dynamic braking amount is too large.

Use a dynamic resistor with a larger ca-

 

 

 

 

 

 

 

 

 

pacity (W) and adjust

(PBR ca-

 

 

 

 

 

 

 

 

 

pacity parameter) accordingly.

 

 

 

 

10h

Overheat

The cooling fan does not rotate.

Restart the operation by resetting the

 

 

 

 

 

The ambient temperature is too high.

 

inverter after it has cooled down enough.

 

 

 

 

 

The vent is blocked up.

 

The fan requires replacement if it does

 

 

 

 

 

A heat generating device is installed close

 

not rotate during operation.

 

 

 

 

 

 

 

 

to the inverter.

 

Secure sufficient space around the

 

 

 

 

 

The thermistor in the unit is broken.

 

inverter.

 

 

 

 

 

 

 

 

 

 

 

Do not place any heat-generating device

 

 

 

 

 

 

 

 

 

near the inverter.

 

 

 

 

 

 

 

 

 

 

Make a service call.

 

 

13

 

 

 

 

 

 

 

 

 

 

*

1E

Undervoltage trip

The input voltage (in the main circuit) is

Check the input voltage.

 

 

 

 

 

(main circuit)

 

too low.

 

Enable

(undervoltage trip selec-

 

 

 

 

 

 

 

 

 

tion).

 

 

 

 

 

 

 

 

 

 

 

To cope with a momentary stop due to

 

 

 

 

 

 

 

 

 

undervoltage, enable

(ride-through

 

 

 

 

 

 

 

 

 

control) and

(auto-restart).

*With a parameter, you can choose between trip-on and -off. (Continued overleaf)