E6580757
3)Switching using external terminals - Switching the acceleration/deceleration time via external termi- nals
Output frequency [Hz]
(1) | (2) | (3) | (4) |
AD2 switching
Time [sec]
(1) Acceleration at the gradient corresponding to acceleration time
(2) Acceleration at the gradient corresponding to acceleration
6 | time |
|
(3)Deceleration at the gradient corresponding to deceleration time
(4)Deceleration at the gradient corresponding to deceleration time
In this case, set " " to 0 (terminal board).
A switching signal for the acceleration/deceleration 2 is not set as the default.
Assign function number 5 () to an idle terminal by specifying the input terminal function selection parameter.
6.15Protection functions
6.15.1Setting motor electronic thermal protection
: Motor electronic thermal protection level 1
• Function
This parameter allows selection of the appropriate electronic thermal protection characteristics ac- cording to the particular rating and characteristics of the motor.
The " " parameter and extended parameter have the same function. Modification of either parameter means that the same value is set for both parameters.
■Parameter setting
Title |
| Function |
|
| Adjustment range | Default setting | |
|
|
|
|
|
|
| |
|
| Motor electronic thermal protection | 10 | ∼ | 100 (%) | 100 | |
( | ) | level 1 | |||||
|
|
|
|