| E6580757 |
|
|
|
|
|
|
|
|
|
|
|
| (Continued) |
|
|
|
|
|
|
|
| Error code | Communication | Problem |
| Possible causes |
|
|
| Remedies |
|
| No. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
* | 1D | • The output current falls to the |
| • | Enable | ||||
|
|
| tion trip |
| detection level during operation. |
|
| rameter). |
|
|
|
|
|
|
|
| • Check whether the detection level is set | ||
|
|
|
|
|
|
|
| properly to the system. | |
|
|
|
|
|
|
|
| ( and | ) |
|
|
|
|
|
|
| • If no error is found in the setting, make a | ||
|
|
|
|
|
|
|
| service call. |
|
|
| 22h | Ground fault trip | • A ground fault occurs in the output cable |
| • Check the cable and the motor for ground | |||
|
|
|
|
| or the motor. |
|
| faults. |
|
|
| 11h | Emergency stop | • During automatic operation or remote op- |
| • | Reset the inverter. | ||
|
|
|
|
| eration, a stop command is entered from |
|
|
|
|
|
|
|
|
| the operation panel or a remote input de- |
|
|
|
|
|
|
|
|
| vice. |
|
|
|
|
|
| 15h | Main unit RAM fault | • | The control RAM is defective. |
| • Make a service call. | ||
|
| 16h | Main unit ROM fault | • | The control ROM is defective. |
| • Make a service call. | ||
|
| 17h | CPU fault trip | • | The control CPU is defective. |
| • Make a service call. | ||
|
| 18h | Remote control error | • An error arises during remote operation. |
| • Check the remote control device, cables, | |||
|
|
|
|
|
|
|
| etc. |
|
|
| 29h | Inverter type error | • The control circuit board (main circuit |
| • Make a service call. | |||
|
|
|
|
| board or drive circuit board) is replaced. |
|
|
|
|
|
| 12h | EEPROM fault | • A data writing error occurs. |
| • Turn off the inverter, then turn it on again. | |||
|
|
|
|
|
|
|
| If it does not recover from the error, make | |
|
|
|
|
|
|
|
| a service call. |
|
|
| 28h | • Check the settings of the motor parameters |
|
| to | . | ||
|
|
|
| • Check that the motor is not two or more sizes smaller in capacity than the inverter. | |||||
|
|
|
| • Check that the inverter output cable is not too thin. |
| ||||
|
|
|
| • Check that the motor is not running. |
|
|
| ||
|
|
|
| • Check that the motor is a |
|
*With a parameter, you can choose between trip-on and -off.
[Alarm information] Each message in the table is displayed to give a warning but does not cause the inverter to trip.
Error code | Problem | Possible causes | Remedies |
|
|
|
|
|
|
|
|
(Note 1) | ST terminal OFF | • The | • Close the |
|
|
| Undervoltage in main | • The supply voltage between R, S and T is | • Measure the main circuit supply voltage. |
|
|
| circuit | under voltage. | If the voltage is at a normal level, the |
|
|
|
|
| inverter requires repairing. |
|
|
| Retry in process | • The inverter is in the process of retry. | • The inverter is normal if it restarts after |
|
|
|
| • A momentary stop occurred. | several tens of seconds. |
|
|
|
|
| The inverter restarts automatically. Be |
|
|
|
|
| careful of the machine because it may |
|
|
|
|
| suddenly restart. |
|
|
| Frequency point set- | • The frequency setting signals at points 1 | • Set the frequency setting signals at points |
|
|
| ting error | and 2 are set too close to each other. | 1 and 2 apart from each other. |
|
|
| Clear command ac- | • This message is displayed when pressing | • Press the STOP key again to clear the |
|
|
| ceptable | the STOP key while an error code is dis- | trip. |
|
|
| 13 | ||||
|
| played. |
|
| |
| Emergency stop | • The operation panel is used to stop the | • Press the STOP key for an emergency |
| |
| command accept- | operation in automatic control or remote | stop. |
| |
| able | control mode. | To cancel the emergency stop, press any |
|
|
|
|
| other key. |
|
|
| Setting error alarm / | • An error is found in a setting when data is | • Check whether the setting is made cor- |
|
|
| An error code and | reading or writing. | rectly. |
|
|
| data are displayed |
|
|
|
|
| alternately twice |
|
|
|
|
| each. |
|
|
|
|
(Continued overleaf)