E6580757

Operation mode parameters

Title

Communication

Function

Unit

Minimum

Adjustment range

Default

User

Reference

 

 

 

No.

 

 

setting unit

 

setting

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0300

PWM carrier

kHz

0.1

2.0-16.5

12.0

 

6.11

 

 

 

 

frequency

 

 

 

 

 

 

 

 

 

0301

Auto-restart

-

-

0: Disabled

0

 

6.12.1

 

 

 

 

control selection

 

 

1: At auto-restart after momentary stop

 

 

 

 

 

 

 

 

 

 

2: When turning ST-CC on or off

 

 

 

 

 

 

 

 

 

 

3: At auto-restart or when turning

 

 

 

 

 

 

 

 

 

 

ST-CC on or off

 

 

 

 

 

 

 

 

 

 

4: Motion of DC braking at start-up

 

 

 

 

 

 

 

 

 

 

(at auto-restart after momentary

 

 

 

 

 

 

 

 

 

 

stop)

 

 

 

 

 

 

 

 

 

 

5: Motion of DC braking at start-up

 

 

 

 

 

 

 

 

 

 

(when turning ST-CC on or off)

 

 

 

 

 

 

 

 

 

 

6: Motion of DC braking at start-up

 

 

 

 

 

 

 

 

 

 

(at auto-restart or when turning

 

 

 

 

 

 

 

 

 

 

ST-CC on or off)

 

 

 

 

 

 

0302

Regenerative

-

-

0: Disabled

0

 

6.12.2

 

 

 

 

power ride-

 

 

1: Enabled

 

 

 

 

 

 

 

through control

 

 

 

 

 

 

 

 

 

0303

Retry selection

Times

1

0-10

0

 

6.12.3

 

 

 

 

(number of times)

 

 

 

 

 

 

 

 

 

0304

Dynamic braking

-

-

0: Dynamic braking disabled

0

 

6.12.4

 

 

 

 

selection

 

 

1: Dynamic braking enabled, over-

 

 

 

 

 

 

 

 

 

 

load protection disabled

 

 

 

 

 

 

 

 

 

 

2: Dynamic braking enabled, over-

 

 

 

 

 

 

 

 

 

 

load protection enabled

 

 

 

 

 

 

0305

Overvoltage limit

-

-

0: Enabled

0

 

6.12.5

 

 

 

 

operation

 

 

1: Prohibited

 

 

 

 

 

 

0306

Output voltage

V

1

0 to 250V, 0 to 500V

200V/400V

 

6.12.6

 

 

 

 

adjustment (Base

 

 

 

 

 

 

 

 

 

 

frequency voltage)

 

 

 

 

 

 

 

 

 

0307

Supply voltage

-

-

0: Supply voltage uncorrected, output

1

 

6.12.6

 

 

 

 

correction

 

 

voltage limited

 

 

 

 

 

 

 

 

 

 

1: Supply voltage corrected, output

 

 

 

 

 

 

 

 

 

 

voltage limited

 

 

 

 

 

 

 

 

 

 

2: Supply voltage corrected (off dur-

 

 

 

 

 

 

 

 

 

 

ing deceleration), output voltage

 

 

 

 

 

 

 

 

 

 

limited

 

 

 

 

 

 

 

 

 

 

3: Supply voltage uncorrected, output

 

 

 

 

 

 

 

 

 

 

voltage unlimited

 

 

 

 

 

 

 

 

 

 

4: Supply voltage corrected, output

 

 

 

 

 

 

 

 

 

 

voltage unlimited

 

 

 

 

 

 

 

 

 

 

5: Supply voltage corrected (off dur-

 

 

 

 

 

 

 

 

 

 

ing deceleration), output voltage

 

 

 

 

 

 

 

 

 

 

unlimited

 

 

 

 

11

 

0308

Braking resistor

%ED

1

1-100

3

 

6.12.4

 

 

 

operation rate

 

 

 

 

 

 

 

 

0312

Random mode

-

-

0: Disabled

0

 

6.11

 

 

 

 

 

 

 

1: Enabled

 

 

 

 

 

 

0360

PI control

-

-

0: Disabled

0

 

6.12.7

 

 

 

 

 

 

 

1: Enabled

 

 

 

 

 

 

0362

Proportional gain

-

-

0-01-100.0

0.30

 

6.12.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0363

Integral gain

-

-

0.01-100.0

0.20

 

6.12.7

 

 

 

 

 

 

 

 

 

 

 

 

 

K-5

Page 172
Image 172
Toshiba VF-S9 manual Operation mode parameters