6.12.3 Retry function

E6580757

6.12.3 Retry function

Manual background : Retry selection (Selecting the number of times the motor is to be restarted automatically)

Manual background Warning

Do not go near the motor in alarm-stop status when the retry function is selected. The motor may suddenly restart, which could result in injury.

Mandatory Take measures for safety, e.g. attach a cover to the motor, to prevent accidents if the motor suddenly re- starts.

Function

This parameter resets the inverter automatically when the inverter gives an alarm. During the retry mode, the motor speed search function operates automatically as required and thus allows smooth motor restarting.

 

 

[Parameter setting]

 

 

 

 

 

 

 

 

Title

 

Function

 

 

Adjustment range

Default setting

6

 

 

 

 

 

 

 

 

 

 

 

 

 

Retry selection

 

0: None, 1

10 times

 

0

 

 

 

 

 

 

 

The likely causes of tripping and the corresponding retry processes are listed below.

 

 

 

 

 

 

Cause of tripping

 

Retry process

 

Canceling conditions

 

 

 

 

 

 

 

 

Momentary power

Up to 10 times in succession

 

The retry function will be canceled at

 

 

failure

1st retry: About 1 sec after tripping

once if tripping is caused by an unusual

 

 

Overcurrent

2nd retry: About 2 sec after tripping

event other than: momentary power fail-

 

 

Overvoltage

3rd retry: About 3 sec after tripping

ure, overcurrent, overvoltage or overload.

 

 

Overload

 

 

This function will also be canceled if re-

 

 

 

 

10th retry: About 10 sec after tripping

trying is not successful within the speci-

 

 

 

 

 

 

 

 

fied number of times.

 

The retry function is disabled in the following unusual events:

: Arm overcurrent at start-up

: Main unit RAM fault

: Overcurrent on the load side at start-up

: Main unit ROM fault

: Output phase failure

: CPU fault trip

: External thermal trip

: Remote control error

: Overtorque trip

: EE PROM fault

: Small-current operation trip

: Auto-tuning error

: External trip stop

 

 

: Undervoltage trip (main circuit)

: Ground fault trip

: Input phase failure

: Inverter type error

Protective operation detection relay signals (FLA, FLB, FLC terminal signals) are not sent during use of the retry function.

A virtual cooling time is provided for overload tripping (Manual background , Manual background , Manual background ). In this case, the retry func- tion operates after the virtual cooling time and retry time.

In the event of over voltage tripping ( Manual backgroundManual background ), re-tripping may result unless the DC voltage de-

F-26