6.12.3 Retry function
: Retry selection (Selecting the number of times the motor is to be restarted automatically)
Warning
•Do not go near the motor in
Mandatory • Take measures for safety, e.g. attach a cover to the motor, to prevent accidents if the motor suddenly re- starts.
• Function
This parameter resets the inverter automatically when the inverter gives an alarm. During the retry mode, the motor speed search function operates automatically as required and thus allows smooth motor restarting.
|
| [Parameter setting] |
|
|
|
|
|
| |
|
| Title |
| Function |
|
| Adjustment range | Default setting | |
6 |
|
| |||||||
|
|
|
|
|
|
|
|
| |
|
| Retry selection |
| 0: None, 1 ∼ | 10 times |
| 0 | ||
|
|
|
|
| |||||
|
| The likely causes of tripping and the corresponding retry processes are listed below. |
| ||||||
|
|
| |||||||
|
| Cause of tripping |
| Retry process |
| Canceling conditions | |||
|
|
|
|
|
| ||||
|
| Momentary power | Up to 10 times in succession |
| The retry function will be canceled at | ||||
|
| failure | 1st retry: About 1 sec after tripping | once if tripping is caused by an unusual | |||||
|
| Overcurrent | 2nd retry: About 2 sec after tripping | event other than: momentary power fail- | |||||
|
| Overvoltage | 3rd retry: About 3 sec after tripping | ure, overcurrent, overvoltage or overload. | |||||
|
| Overload |
| … |
| This function will also be canceled if re- | |||
|
|
|
| 10th retry: About 10 sec after tripping | trying is not successful within the speci- | ||||
|
|
|
|
|
|
|
| fied number of times. |
|
★The retry function is disabled in the following unusual events:
• | : Arm overcurrent at | • | : Main unit RAM fault |
• | : Overcurrent on the load side at | • | : Main unit ROM fault |
• | : Output phase failure | • | : CPU fault trip |
• | : External thermal trip | • | : Remote control error |
• | : Overtorque trip | • | : EE PROM fault |
• | : | • | : |
• | : External trip stop |
|
|
• | : Undervoltage trip (main circuit) | • | : Ground fault trip |
• | : Input phase failure | • | : Inverter type error |
★Protective operation detection relay signals (FLA, FLB, FLC terminal signals) are not sent during use of the retry function.
★A virtual cooling time is provided for overload tripping ( , , ). In this case, the retry func- tion operates after the virtual cooling time and retry time.
★In the event of over voltage tripping ( ∼ ),