Toshiba VF-S9 automatic torque boost and V/F control mode selection, auto-tuning is set to 2. ⇒

Models: VF-S9

1 198
Download 198 pages 1.97 Kb
Page 64
Image 64
(auto-tuning) is set to 2. ⇒

 

 

 

 

 

E6580757

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Key operated

LED display

 

Operation

 

 

 

 

 

 

 

 

 

 

 

Press the

key to change the parameter to 1 (sensorless vector

 

 

 

 

control + auto-tuning).

 

 

 

 

 

Press the ENTER key to save the changed parameter.

and

 

 

 

 

the parameter are alternately displayed.

 

 

Note 1: Setting V/F control selection to automatically programs to If the desired torque cannot be obtained, see 6.13, 3. (sensorless vector control) provides the same characteristics as

when

(auto-tuning) is set to 2.

See 5.12

Note 2: Setting

to automatically programs

to .

If vector control cannot be programmed....

First read the precautions about vector control in 5.12, 6.

1)

If the desired torque cannot be obtained, see 6.13, 3.

2)

If auto-tuning error "

" appears, see 6.13, 3.

■ (automatic torque boost) and  (V/F control mode selection) (automatic torque boost) and Check the programmed value of (V/F control mode selection)

 

 

 

 

Automatic torque boost is the parameter for setting V/F control mode selection (

) and auto-

 

 

 

 

tuning (

) together. That is why all parameters related to

change automatically when

5

 

 

 

is changed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatically programmed parameters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check the programmed value of

.

 

 

 

 

 

Displays

after resetting

- (If

is not changed, it becomes 0

-

 

 

 

 

 

 

 

(V/F constant) )

 

 

 

 

 

 

Sensorless vector control

 

Sensorless vector control

 

Executed

 

 

 

 

+ auto-tuning

 

 

( after execution)

 

 

 

 

 

 

 

 

2) Increasing torque manually (V/F constant control)

The VF-S9 inverter is set to this control mode by factory default.

This is the setting of constant torque characteristics that are suited for such things as conveyors. It can also be used to manually increase starting torque.

If V/F constant control is programmed after changing 2) Increasing torque manually (V/F constant control),

Set V/F control mode selection The VF-S9 inverter is set to this control mode by factory default. to 0 (V/F constant)

 

 

See 5.12.

Note 1:

If you want to increase torque further, raise the setting value of manual torque boost .

 

How to set manual torque boost parameter

See 5.13.

Note 2:

V/F control selection to 1 (variable torque) is an effective setting for the load on such

 

equipment as fans and pumps.

See 5.12.

E-4

Page 64
Image 64
Toshiba VF-S9 automatic torque boost and V/F control mode selection, Increasing torque manually V/F constant control