■Communication function parameters (Common serial options)

E6580757

Communication function parameters (Common serial options)

The data transfer speed, parity type, inverter number, and communication error trip time can be set/edited by operation panel operation or communication function.

Title

 

Function

Adjustment range

Default setting

 

 

 

 

 

 

 

 

0: 1200bps

 

 

 

 

1: 2400bps

 

 

Data transfer speed

2: 4800bps

3

 

 

 

3: 9600bps

 

 

 

 

4:19200bps

 

 

 

 

0: NON (No parity)

 

 

Parity

(Common serial)

1: EVEN (Even parity)

1

 

 

 

2: ODD (Odd parity)

 

 

Inverter number

0 63

0

 

 

 

 

 

 

Communication error trip time

0: Disabled *

0

 

1 100 (s)

 

 

 

 

*Disabled ........... Indicates that the inverter will not be tripped even if a communication error occurs.

Trip ...................The inverter trips when a communication time-over occurs. In this case a trip information

" 6.17.2 Using the RS232C/RS485 " flashes on and off on the operation panel.

6.17.2 Using the RS232C/RS485

Setting the communication functions

6

Setting commands and frequencies by communications has priority over sending commands from the opera- tion panel or the terminal board. Command/frequency setting by communications can therefore be enabled,

irrespective of the setting in the command mode ( ■Setting the communication functions ) or the frequency setting mode ( ■Transmission specifications ). However, when the input terminal function selection parameter is set to 48: SC/LC (Serial/Local selection),

the inverter can be operated with the settings of the command mode ( Manual background ) or the frequency setting mode

( Manual background ) by external input.

Transmission specifications

Item

Specifications

 

Transmission scheme

Half-duplex

 

 

Connection scheme

Centralized control

 

 

Synchronization scheme

Asynchronous

 

 

Transmission rate

Default: 9600 baud (parameter setting)

 

 

Option: Either 1200, 2400, 4800, 9600, or 19200 baud

 

 

Character transmission

ASCII code: JIS X 0201, 8-bit (fixed)

 

 

Binary code: Binary, 8-bit (fixed)

 

Stop bit length

Inverter receiving: 1 bit, Inverter sending: 2 bits

 

 

Error detection

Parity: Even, Odd, or None selectable by parameter setting;

 

 

 

check sum method

 

 

Character transmission format

Receiving: 11-bit, Sending: 12-bit

 

 

Order of bit transmission

Least significant bit first

 

 

Frame length

Variable to a maximum of 15 bytes

 

 

 

 

 

 

 

F-55