Toshiba VF-S9 manual Increasing starting torque, Motor constant must be set

Models: VF-S9

1 198
Download 198 pages 1.97 Kb
Page 76
Image 76
3) Increasing starting torque

E6580757

3) Increasing starting torque

 

 

 

Setting V/F control selection

to

(automatic torque boost)

 

 

 

Detects load current in all speed ranges and automatically adjusts voltage output (torque boost) from inverter.

 

 

This gives steady torque for stable runs.

 

 

 

 

 

 

 

Base frequency voltage

 

 

 

 

 

 

Output voltage (%)

 

 

 

 

 

 

 

 

Automatically

 

 

 

 

 

 

 

 

adjusts the amount

 

 

 

 

 

 

 

 

of torque boost.

 

 

 

Base frequency

Output frequency (Hz)

 

 

 

 

 

 

 

 

 

 

Note: This control system can oscillate and destabilize runs depending on the load. If that should

 

 

 

happen, set V/F control mode selection

to (V/F constant) and increase torque manually.

5

 

 

Motor constant must be set

 

 

 

 

 

 

 

 

 

 

 

 

 

If the motor you are using is a 4P Toshiba standard motor and if it has the same capacity as the inverter,

 

 

there is basically no need to set the motor constant.

 

 

 

 

 

There are two procedures for setting the motor constant.

 

 

 

1)

The motor constant can be set automatically (auto-tuning). Program the extended parameter

 

 

 

to .

 

 

For details, see selection 2 in 6.13.

 

 

2)

Each motor constant can be set individually.

For details, see selection 3 in 6.13.

4)Sensorless vector control--increasing starting torque and achieving high-precision operation.

Setting of V/F control mode selection happen, set V/F control mode selection to Motor constant must be set (Sensorless vector control)

Using sensorless vector control with a Toshiba standard motor will provide the highest torque at the lowest speed ranges. The effects obtained through the use of sensorless vector control are described below.

(1)Provides large starting torque.

(2)Effective when stable operation is required to move smoothly up from the lowest speeds.

(3)Effective in elimination of load fluctuations caused by motor slippage.

Motor constant must be set

If the motor you are using is a 4P Toshiba standard motor and if it has the same capacity as the inverter, there is basically no need to set the motor constant.

There are three procedures for setting motor constants.

1)

The sensorless vector control and motor constants (auto-tuning) can be set at a time.

 

Set the basic parameter

to .

 

For details, see 1 in 5.2.

2)

The motor constant can be automatically set (auto-tuning).

 

Set the extended parameter

 

to .

For details, see selection 2 in 6.13.

E-16

Page 76
Image 76