E6580757
3) Increasing starting torque
|
|
| Setting V/F control selection | to | (automatic torque boost) |
| ||
|
| Detects load current in all speed ranges and automatically adjusts voltage output (torque boost) from inverter. | ||||||
|
| This gives steady torque for stable runs. |
|
|
|
| ||
|
|
| Base frequency voltage |
|
|
| ||
|
|
| Output voltage (%) |
|
|
|
|
|
|
|
| Automatically |
|
|
|
|
|
|
|
| adjusts the amount |
|
|
|
|
|
|
|
| of torque boost. |
|
|
| Base frequency | Output frequency (Hz) |
|
|
|
|
|
|
| ||
|
|
| Note: This control system can oscillate and destabilize runs depending on the load. If that should | |||||
|
|
| happen, set V/F control mode selection | to (V/F constant) and increase torque manually. | ||||
5 |
|
| ||||||
★ | Motor constant must be set |
|
|
|
|
| ||
|
|
|
|
|
| |||
|
| If the motor you are using is a 4P Toshiba standard motor and if it has the same capacity as the inverter, | ||||||
|
| there is basically no need to set the motor constant. |
|
|
| |||
|
| There are two procedures for setting the motor constant. |
| |||||
|
| 1) | The motor constant can be set automatically | |||||
|
|
| to . |
|
| ⇒ | For details, see selection 2 in 6.13. | |
|
| 2) | Each motor constant can be set individually. | ⇒ | For details, see selection 3 in 6.13. |
4)Sensorless vector
Setting of V/F control mode selection to (Sensorless vector control)
Using sensorless vector control with a Toshiba standard motor will provide the highest torque at the lowest speed ranges. The effects obtained through the use of sensorless vector control are described below.
(1)Provides large starting torque.
(2)Effective when stable operation is required to move smoothly up from the lowest speeds.
(3)Effective in elimination of load fluctuations caused by motor slippage.
★Motor constant must be set
If the motor you are using is a 4P Toshiba standard motor and if it has the same capacity as the inverter, there is basically no need to set the motor constant.
There are three procedures for setting motor constants.
1) | The sensorless vector control and motor constants | ||||
| Set the basic parameter | to . |
| ⇒ | For details, see 1 in 5.2. |
2) | The motor constant can be automatically set | ||||
| Set the extended parameter |
| to . | ⇒ | For details, see selection 2 in 6.13. |