E6580757

<<Sample sequence diagram 2: Adjustment with pulse signals>>

RUN command

Incrementing (UP) signal

Decrementing (DOWN)signal

Set frequency clearing signal

Upper limit frequency

OHZ

6

■ Simultaneous input

 

 

 

If input clearing signal and decrementing signal at the same time, clearing signal is allowed.

 

If input incrementing signal and decrementing signal at the same time, difference of both signal is re-

 

 

sponded.

 

 

 

 

 

 

Ex. If

>

frequency (

-

) increase.

■ Storage of the set frequency

Set parameter = to select automatic storage of the frequency setting.

Frequency adjustment range

The frequency can be set from (lower limit frequency) to (upper limit frequency). The value will be set as soon as the set frequency clearing function (function number: 43, 44) is entered from the input terminal.

Minimum unit of frequency adjustment

If the unit selection parameter = 2 (free unit selection enabled) and the free unit selection pa-

rameter = 1.00, the output frequency can be adjusted in steps of 0.01Hz.