E6580757
6.15.9 Undervoltage trip
: Undervoltage trip selection
• Function
This parameter is used for selecting the control mode when an undervoltage is detected. Trip infor-
mation is displayed as “ “.
(Disabled).......The inverter is stopped. However, it is not tripped (FL relay deactivated).
The inverter is stopped when the voltage does not exceed 70% or less of its rating.
(Enabled) .......The inverter is stopped. It is also tripped (FL relay activated), only after detec-
tion of a voltage not exceeding 70% or less of its rating. (Disabled).......Control is continued even at 60% of the rated voltage.
The inverter stop (FL relay deactivated), only after detection of a voltage not ex- ceeding 45% of its rating.
An input AC reactor must be used. See 10.4.
Title | Function | Adjustment range | Default setting |
|
|
|
|
|
| 0: Disabled |
|
| Undervoltage trip selection | 1: Enabled (Trip at 70% or less) | 0 |
| 2: Disabled (Stop(not trip) at 45% or less, | ||
|
|
| |
|
| optional) |
|
6
6.15.10 4-20mA dc calibration
: Meter bias
• Function
Output signals from FM terminals are analog voltage signals. Their standard setting range is from 0 to 1mAdc or from 0 to 7.5Vdc.
These standard setting ranges can be switched to
Title | Function | Adjustment range | Default setting |
|
|
|
|
| Meter bias | 0 ∼ 50 (%) | 0 |
Note: Use the jumper pin (JP302) to select FMC