6.15.9 Undervoltage trip

E6580757

6.15.9 Undervoltage trip

: Undervoltage trip selection

Function

This parameter is used for selecting the control mode when an undervoltage is detected. Trip infor-

mation is displayed as “ : Undervoltage trip selection “.

6.15.10 4-20mA dc calibration (Disabled).......The inverter is stopped. However, it is not tripped (FL relay deactivated).

The inverter is stopped when the voltage does not exceed 70% or less of its rating.

 : Meter bias (Enabled) .......The inverter is stopped. It is also tripped (FL relay activated), only after detec-

tion of a voltage not exceeding 70% or less of its rating. Manual background (Disabled).......Control is continued even at 60% of the rated voltage.

The inverter stop (FL relay deactivated), only after detection of a voltage not ex- ceeding 45% of its rating.

An input AC reactor must be used. See 10.4.

Title

Function

Adjustment range

Default setting

 

 

 

 

 

 

0: Disabled

 

 

Undervoltage trip selection

1: Enabled (Trip at 70% or less)

0

 

2: Disabled (Stop(not trip) at 45% or less,

 

 

 

 

 

optional)

 

6

6.15.10 4-20mA dc calibration

Manual background : Meter bias

Function

Output signals from FM terminals are analog voltage signals. Their standard setting range is from 0 to 1mAdc or from 0 to 7.5Vdc.

These standard setting ranges can be switched to 0-20mAdc by changing the position of the required jumper pin (JP302) in the inverter main unit. Calibration for 4-20mA dc output is possible by setting this parameter.

Title

Function

Adjustment range

Default setting

 

 

 

 

 

Meter bias

0 50 (%)

0

Note: Use the jumper pin (JP302) to select FMC (0-20mA dc (4-20mA dc)) output.

F-49