2) Emergency stopping from the operation panel
Emergency stopping from the operation panel is possible by pressing the STOP key on the panel twice while
the inverter is not in the panel control mode. |
|
| |
(1) | Press the STOP key | " | " will blink. |
(2) | Press the STOP key once again | Operation will come to a trip stop in accordance with the setting | |
|
| of the | parameter. After this, " " will be displayed and a |
|
| failure detection signal generated (FL relay deactivated). |
6.15.5 Output phase failure detection
: Output phase failure detection mode selection
• Function |
|
| |
This parameter detects inverter output Phase failure. If the Phase failure status persists for one sec- | |||
ond or more, the tripping function and the FL relay will be activated. At the same time, the trip infor- | |||
mation | will also be displayed. |
|
|
Set | to " " to control the opening of the inverter connection to the motor and connecting | ||
commercial power to the motor. |
|
| |
|
|
| 6 |
Detection errors may occur for special motors such as |
| ||
| (Disabled) |
|
|
................................ | No tripping (FL relay deactivated). |
| |
| (Enabled during operation) |
|
|
................................ | Phase failure detection is enabled during operation. The inverter will trip if the | ||
| Phase failure status persists for one second or more. (FL relay activated.) | ||
| (Enabled; Disabled during |
|
|
................................ | This function, however, is disabled during | ||
| ure. When phase failure detect decrease the output voltage, and restart. | ||
Title | Function | Adjustment range | Default setting |
|
| 0: Disabled |
|
| Output phase failure detection mode | 1: Enabled (during operation) |
|
|
|
| 0 |
| selection | 2: Enabled |
|
|
| (Disabled during |
|