E6580757

creases below a predetermined level.

In the event of overheating-caused tripping ( ), re-tripping may result unless the internal temperature decreases below a predetermined level, since the internal temperature detection function of the inverter works.

Even when trip retention selection parameter is set to " ", the retry function is enabled by setting.

During retrying, the blinking display will alternate between " " and the monitor display specified by

status monitor display mode selection parameter .

6.12.4 Dynamic (regenerative) braking

: Dynamic braking selection

: Braking resistor operation rate

Function

The VFS9 does not contain a braking resistor. Connect an external braking resistor in the following

 

cases to enable dynamic braking:

 

6

1)

when decelerating the motor abruptly or if overvoltage tripping (OP) occurs during deceleration

 

 

stop

 

 

 

2)

when a continuous regenerative status occurs during downward movement of a lift or the wind-

 

 

ing-out operation of a tension control machine

 

3)

when the load fluctuates and a continuous regenerative status results even during constant

 

 

speed operation of a machine such as a press

 

[Parameter setting]

Title

Function

Adjustment range

Default setting

 

 

 

 

 

 

0: Dynamic braking disabled

 

 

 

1: Dynamic braking enabled, overload

 

 

Dynamic braking selection

protection disabled

0

 

 

2: Dynamic braking enabled, overload

 

 

 

protection enabled

 

 

Braking resistor operation rate

1 100 (% ED)

3

F-27

Page 111
Image 111
Toshiba VF-S9 manual Dynamic regenerative braking, Dynamic braking selection Braking resistor operation rate